Technical Data<strong>P12x</strong>/<strong>EN</strong> TD/<strong>Eb6</strong>MiCOM P120/P121/P122/P123 Page 19/509.6.1 Multishot Autoreclose Settings[79] AutorecloseSetting rangeMin Max StepAutoreclose ?Yes or NoExt. CB Fail ?Yes or NoExt. CB Fail time 0.01 s 600 s 0.01 sExt Block ?Yes or NoRolling demand ?Yes or NoMaximum cycle number 2 100 1Time period 10mn 24h 10mnDead timetD1 0.01 s 300 s 0.01 stD2 0.01 s 300 s 0.01 stD3 0.01 s 600 s 0.01 stD4 0.01 s 600 s 0.01 sMinimum drop off timetI> 50ms 600s 10mstI>> 50ms 600s 10mstI>>> 50ms 600s 10mstIe> 50ms 600s 10mstIe>> 50ms 600s 10mstIe>>> 50ms 600s 10msReclaim Time tR 0.02 s 600 s 0.01 sInhib timePhase Cycles 0 4 1E/Gnd Cycles 0 4 1Cycles 4 3 2 1 SettingstI> 1 1 1 1 0 or 1 or 2 or 3tI>> 1 1 1 1 0 or 1 or 2 or 3tI>>> 1 1 1 1 0 or 1 or 2 or 3tIe> 1 1 1 1 0 or 1 or 2 or 3tIe>> 1 1 1 1 0 or 1 or 2 or 3tIe>>> 1 1 1 1 0 or 1 or 2 or 3tAux1 1 1 1 1 0 or 1 or 2 or 3tAux2 1 1 1 1 0 or 1 or 2 or 30 = no action on autorecloser : definitive trip1 = trip on pick up of the protection element, followed by reclosing cycle2 = no trip on pick up of the protection element also if this has been set in the CRTL/Tripcommands/Trip menu.3 = autoreclose without trip (trip order inhibited, no trip order from autoreclose function).