<strong>P12x</strong>/<strong>EN</strong> FT/<strong>Eb6</strong>Page 34/62User GuideMiCOM P120/P121/P122/P1232.8.5 Submenu [37] UNDERCURR<strong>EN</strong>T Protection (P122 & P123 only)Undercurrent function will:− start as soon as the current of one phase is below I< threshold value (OR of the 3 phasescurrent)− trip if the current of one phase - at least - remains below this threshold during more thantI