User Guide<strong>P12x</strong>/<strong>EN</strong> FT/<strong>Eb6</strong>MiCOM P120/P121/P122/P123 Page 43/62T Inrush reset =0 msBlocking Inrush FunctionNoSet the value for the Inrush tReset time. This provides areset delay of the Inrush Blocking signal (logic state=1)once the 2 nd harmonic level falls below the set threshold.The setting range is from 0.0s to 2 s (step 10ms). Use to change setting and press to validate yourchoice.Enables or disables Inrush blocking for the function.Refer to previous tables for protection functions list.2.9.5 Submenus Logic Select (P122 & P123 only)With the submenu Logic Select. 1 or Logic Select. 2, the user can assign each time delaythreshold to the "Log Sel" input (refer to Inputs menu).Setting Yes or No enables or disables Logic Selectivity 1 of the following protectionfunctions:AUTOMAT. CTRLLogic Select. 1Heading of the Logic Select. 1 submenu.Sel1 tI>>Sel1 tI>>>Sel1 tIe>>Sel1 tIe>>>Sel1 tIe>>>>t Sel1Yes/NoYes/NoYes/NoYes/NoYes/No20 msTime delayed second phase overcurrent threshold (tI>>).Time delayed third phase overcurrent threshold (tI>>>).Second earth fault time delay overcurrent threshold(tIe>>).Third earth fault time delay overcurrent threshold(tIe>>>).Derived earth overcurrent threshold (tIe>>>>).Set the selective scheme logic time delay t Sel1, from 0sto 150s (step 10ms).2.9.6 Outputs Relays submenuThis submenu makes it possible to assign various alarm and trip thresholds (instantaneousand/or time delay) to a logic output. Setting choice: 1 assigns the output relay; 0 noassignment, i.e. output signal trip (RL1) in the following list is assigned to output 3 (RL3), 7(RL7) and 8 (RL8).Excepted from this option are the Watchdog (RL0) and the Tripping (RL1) outputs (refer toTrip Commands submenu).The total number of programmable logic outputs for the four relay models is listed in thetable:Model P120 P121 P122 P123Output relays 3 3 5 7RL2 relay is a change over relay. The others RL3 to RL8 are normally open relays.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!