Technical Data<strong>P12x</strong>/<strong>EN</strong> TD/<strong>Eb6</strong>MiCOM P120/P121/P122/P123 Page 23/5010.8.2 Auxiliary timesAuxiliary timersSetting rangeMin Max StepAux1 time tAux1 0 200s 10msAux2 time tAux2 0 200s 10msAux3 time tAux3 0 200s 10msAux4 time tAux4 0 200s 10msAux5 time tAux5 0 200s 10ms10.9 Broken Conductor Detection (P122 & P123)Principle used:Functionality available for:I2/I1(IA or IB or IC) > 10% In10.9.1 Broken Conductor Detection Setting RangesBroken ConductorSetting rangeMin Max StepBrkn.Cond ?Yes or NoRatio I2/I1 20% 100% 1%Brkn.Cond Time tBC 1s 14400s 1s10.10 Cold Load Pickup (P122 & P123)Cold Load PUSetting rangeMin Max StepCold Load PU ?Yes or NoCLPU Start inputYes or NoCLPU Start autoYes or NoCold load PU level 20% 800% 1%Cold load PU tCL 100ms 3600s 10ms10.11 Circuit Breaker Failure (P122 & P123)10.11.1 CB Fail Setting RangesCB FailSetting rangeMin Max StepCB Fail ?Yes or NoI< 0.02 In 1In 0.01 InCB Fail Time tBF 10 ms 10 s 0.01 sBlock I> No Yes Yes or NoBlock Ie> No Yes Yes or No