13.07.2015 Views

P12x/EN T/Eb6 - Schneider - error

P12x/EN T/Eb6 - Schneider - error

P12x/EN T/Eb6 - Schneider - error

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>P12x</strong>/<strong>EN</strong> TD/<strong>Eb6</strong>Page 12/50Technical DataMiCOM P120/P121/P122/P1234. <strong>EN</strong>VIRONM<strong>EN</strong>TTemperature IEC 60068-2-1 : 1993 Storage –25 °C to +70 °CIEC 60068-2-2: 1993 Operation: –25 °C to + 55 °C–25°C to 70° (*)(*) The upper limit is permissible for a single 6hour duration within any 24 hour period.Humidity dam heat IEC 60068-2-78:2001 56 days at 93% RH and 40 °CEnclosure protection IEC 60-529: 2001 Dust IP50 (whole case), Front IP 52,Back IP 10Sinusoidal Vibrations IEC 60255-21-1:1998 Response and endurance, class 2Shocks IEC 60255-21-2:1998 Response and withstand, class 2Shock withstand & Bump IEC 60255-21-2:1998 Response and withstand, class 1Seismic IEC 60255-21-3:1993 Class 2Corrosive Environments :Per IEC 60068-2-60: 1995, Part 2, Test Ke, Method (class) 3Industrial corrosive environment/poor environmental control, mixed gas flow test.21 days at 75% relative humidity and +30°CExposure to elevated concentrations of H²S, NO², Cl² and SO².

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!