<strong>P12x</strong>/<strong>EN</strong> CT/<strong>Eb6</strong> CommunicationsIEC 60870-5-103 DATABASEPage 18 MiCOM P120/P121/P122/P123The disturbance record mapping for P122 and P123 is the following:−Number of analog channels transmitted: 4, which are:Channel 1: Ia current (Phase L1).Channel 2: Ib current (Phase L2).Channel 3: Ic current (Phase L3).Channel 4: IN current (Earth).− Identifiers of tags (13) transmitted in ASDU 29 (logical informations) for P122:− Tag number 1: IN>: FUN INF − Tag number 2: General start: FUN INF − Tag number 3: CB Failure: FUN INF − Tag number 4: General Trip: FUN INF − Tag number 5: tI>: FUN INF − Tag number 6: tI>>: FUN INF − Tag number 7: tI>>>: FUN INF with private option inactive: FUN ,INF − Tag number 8: tIN> (Earth): FUN INF − Tag number 9: tIN>> (Earth): FUN INF − Tag number 10: tIN>>> (Earth): FUN INF with private option inactive: FUN ,INF − Tag number 11: Log input 1: FUN INF with private option inactive: FUN ,INF − Tag number 12: Log input 2: FUN INF