<strong>P12x</strong>/<strong>EN</strong> CT/<strong>Eb6</strong>MODBUS DatabasePage 42CommunicationsMiCOM P120/P121/P122/P1234. DESCRIPTION OF THE MAPPING FORMAT, MiCOM P122 AND P123CODEDESCRIPTIONF1 Unsigned integer – numerical data: 0 to 65535F2 Signed integer – numerical data: -32768 to 32767F3aF3bF4F5Unsigned integer – curves type0: STI (IEC)1: SI (IEC)2: VI (IEC)3: EI (IEC)4: LTI (IEC)5: STI (C02)6: MI (ANSI)7: LTI (CO8)8: VI (ANSI)9: EI (ANSI)10: RC (IEC) Rectifier curve11: BPN (EDF)Unsigned integer – RXIDG curve type0 : curve 1 (K = 0.3)1 : curve 2 (K = 0.4)2 : curve 3 (K= 0.5)3 : curve 4 (K = 0.6)4 : curve 5 (K = 0.7)5 : curve 6 (K = 0.8)6 : curve 7 (K = 0.9)7 : curve 8 (K = 1.0)Unsigned integer: MODBUS speed0: 3001: 6002: 12003: 24004: 48005: 96006: 192007: 38400Unsigned integer: parity0: without1: even2: odd