Application Guide<strong>P12x</strong>/<strong>EN</strong> AP/<strong>Eb6</strong>MiCOM P120/P121/P122/P123 Page 45/78It is essential to set correctly the time delay associated to this function. It should also benoted that this element is used primarily as a back-up protection to other protective devicesor to provide an alarm. Therefore, this function is usually set with a long time delay.Care must be made to ensure that the time delay is set above the operating time of anyother protection device (at minimum fault level) present on the system and that may react tounbalanced faults, such as:• Phase overcurrent elements• Earth fault elements• Broken conductor elements• Negative phase sequence influenced thermal protection elementstI2> and tI2>> timers associated to I2 threshold can be set under the menu PROTECTION7G1(2)/[46] Neg Seg OC.