<strong>P12x</strong>/<strong>EN</strong> CT/<strong>Eb6</strong>DNP 3.0 DatabasePage 10CommunicationsMiCOM P120/P121/P122/P123Binary Input PointsStatic (Steady-State) Object Number: 1Change Event Object Number: 2Request Function Codes supported: 1 (read)Static Variation reported when variation 0 requested: 1 (Binary Input without status)Change Event Variation reported when variation 0 requested: 1 for P120 et P121 and2 (Binary Input Change withTime) for P122 and P123P120PointIndexP121PointIndexP122PointIndexP123PointIndexName/Descriptioninit val.ChangeEvent Class(1, 2, 3 ornone)88 taux4 alarm(if latched by Trip) 0 389 Final trip (autorecloser) 0 139 79 90 t Equation A 0 140 80 91 t Equation B 0 141 81 92 t Equation C 0 142 82 93 t Equation D 0 143 83 94 t Equation E 0 144 84 95 t Equation F 0 145 85 96 t Equation G 0 146 86 97 t Equation H 0 187 98 Blocking inrush 0 147 88 99 t Equation A (latched) 0 348 89 100 t Equation B (latched) 0 349 90 101 t Equation C (latched) 0 350 91 102 t Equation D (latched) 0 351 92 103 t Equation E (latched) 0 352 93 104 t Equation F (latched) 0 353 94 105 t Equation G (latched) 0 354 95 106 t Equation H (latched) 0 3