4.9.1 Module 9100: Assign data interface<br />

Module 9100 assigns one of the interfaces (RS-232-C/V.24 or RS-422/V.11, for <strong>TNC</strong> <strong>360</strong> the<br />

RS-232-C) to the PLC, configures the transfer parameters and switches the interface to receive<br />

mode. The interface is also initialized and any fault indicators are reset. The data interface cannot be<br />

used by the input/output program of the NC operator interface because it is assigned to the PLC.<br />

The following constraints should be observed:<br />

- The assignment of an interface to the PLC is canceled whenever the PLC program is transferred.<br />

- Configuration for 19 200 baud is not possible. The baud rate is set in MP 9040. The data format is<br />

7 data bits, one even parity bit.<br />

Module call:<br />

PS K/B/W/D Interface 0 = RS-232-C/V.24<br />

(1 = RS-422/V.11)<br />

CM 9100<br />

If the module is incorrectly processed the interface is not assigned to the PLC and marker M3171 is<br />

set.<br />

Potential errors:<br />

- The interface is already assigned by the input/output program of the user interface.<br />

- The call parameters of the module are outside the permitted range.<br />

- The required baud rate is not available because of the way the other serial interface is<br />

configured. (19 200 baud).<br />

4.9.2 Module 9101: Enable data interface<br />

Module 9101 cancels the assignment of an interface to the PLC and makes it again available for the<br />

user's interface input/output program. Interface receive readiness is canceled.<br />

Module call:<br />

PS K/B/W/D Interface 0 = RS-232-C/V.24<br />

(1 = RS-422/V.11)<br />

CM 9101<br />

Marker M3171 is set if the assignment is not canceled.<br />

Potential errors:<br />

- The interface was not assigned to the PLC.<br />

- The call parameters of the module are outside the permitted range.<br />

7-110 <strong>TNC</strong> <strong>360</strong> 4 PLC Modules 8/95