APPENDIX A<br />

Existing Pump Stations and Generator Requirements<br />

Field Data<br />

Nameplate<br />

Horsepower<br />

Horsepower<br />

Based On<br />

Inrush Amps<br />

Pump Station<br />

# of<br />

Pumps<br />

F/L<br />

Amps<br />

Inrush<br />

Amps<br />

Phase/<br />

Volts<br />

Gen Size<br />

(KW)<br />

437 2 40 20 30 287 3/480 80<br />

438 2 5 9.5 86 3/480 20<br />

439 2 7.5 22 107 3/240 40<br />

441 2 2 5 47 3/240 10<br />

442 2 15 10 15.2 148 3/480 60<br />

443 2 20 34.5 61 3/480 80<br />

444 2 50 62 386 3/480 100<br />

445 2 10 31 260 3/240 60<br />

446 2 30 20 31 199 3/480 80<br />

447 3 15 26 120 3/480 100<br />

448 2 5 16 113 3/240 20<br />

449 2 15 28 206 3/480 60<br />

450 2 10 16 199 3/480 40<br />

451 2 5 17 79 3/240 20<br />

452 2 30 20 31 214 3/480 80<br />

453 2 20 36.7 202 3/480 80<br />

454 2 7.5 14 120 3/480 40<br />

455 2 50? 20 37 258 3/480 60<br />

456 2 20 12 70 3/240 60<br />

457 2 10 8 22 138 3/240 40<br />

458 2 3 8 50 3/240 20<br />

460 2 20 38 254 3/480 60<br />

500 2 50 60 351 3/480 100<br />

504 2 60 70 433 3/480 125<br />

508 3 50 56 376 3/480 125<br />

601 3 75? 60 53 393 3/480 125<br />

676 3 60 55 418 3/480 125<br />

944 3 75 52 3/480 150<br />

101A 2 10 27 161 3/240 40<br />

332A 2 70 3/480 150<br />

65A 3 77 84.0 3/480 150<br />

Parish Prison 2 2 6.6 34.9 3/240 10<br />

Total No. Generators 287<br />

Notes:<br />

If motors were accessible, motor nameplate data was obtained.<br />

If motors were not accessible, motor running and starting current was measured.<br />

For non-PDP pump stations the number of pumps listed is the number of installed pumps.<br />

It is not clear whether or not 1 pump less than listed is sufficient for the peak wet weather flow.<br />

Generators were sized based on running one pump less than the number listed, except that for pumps 20 hp<br />

and smaller, the generator was sized to run a minimum of 2 pumps.<br />

If the data indicated two different motor sizes, the generator was selected based on the larger motor size.<br />

GNV31031158554.DOCX/103470007 A-7 JANUARY 2011<br />