Forms for Columns 295

For shear, from Eq. (10-4),

l v

= 192F v

bd/15w + 2d

= 192(218.7)(3.5)(1.5)/15(1,172) + 2(1.5)

= 15.5 in.

For deflection not to exceed l/360, from Eq. (10-5),

l ∆

= [1,743EI/360w] 1/3

= [1,743(1,600,000)(0.984)/360(1,172)] 1/3

= 18.6 in.

ww.EasyEngineering.n

For deflection not to exceed ¹⁄16 in., from Eq. (10-6),

l ∆

= [1,743EI/16w] 1/4

= [1,743(1,600,000)(0.984)/16(1,172)] 1/4

= 19.6 in.

Below is a summary of the allowable span lengths of the 2 × 4

vertical wood battens:

For bending, the maximum span length = 16.6 in.

For shear, the maximum span length = 15.5 in.

For deflection, the maximum span length = 18.6 in.

For this example, shear governs the maximum span length of the

wood battens. The spacing of the column clamps at the bottom of the

form must not exceed 15.5 in. For constructability, the spacing would

likely be placed at 12 in. Figure 10-4 shows a plan view of the assembled

forms.

The pressure on the forms is greatest at the bottom, linearly

decreasing to zero at the top of the form, see Eq. (10-1). Therefore, the

spacing of the column clamps may be increased in the upper portion

of the forms. It may be desirable to place the Plyform panel in the

horizontal direction at the bottom of the form, and then place the

panels in the vertical direction in the upper portion of the form where

the concrete pressure is not as great. The procedure illustrated in this

example may be used to calculate the allowable spacing of column

clamps at any height of the column forms, based on the strength and

deflection of the sheathing.

The column clamps must be strong enough to resist the loads

transmitted to them by the sheathing. There are numerous manufacturers

of patented column clamps for forming concrete columns.

These manufacturers generally specify the safe spacing for their particular

clamps. The following sections provide information on patented

clamps.