28.02.2013 Views

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

HEATING, VENTILATION, AND AIR CONDITIONING 13.47<br />

TABLE 13.12 Air-Supply Distribution in Accordance with Heat Load<br />

Space<br />

Load,<br />

Btu per hr % of load<br />

Cfm<br />

(% � 2,010)<br />

Cellar 14,500 10.05 200<br />

First-floor store 47,600 33.00 660<br />

Vestibule 5,650 3.91 80<br />

Office 4,900 3.39 70<br />

Men’s room 2,800 1.94 40<br />

Ladies’ room 1,590 1.10 25<br />

Second-floor office No. 1 33,300 23.01 460<br />

Office No. 2 16,650 11.51 230<br />

Men’s room 2,820 1.95 40<br />

Ladies’ room 2,080 1.44 30<br />

Hall 12,585 8.70 175<br />

144,475 100.00 2,010<br />

q 160,000<br />

�T � � � 73.6�F<br />

1.08Q 1.08 � 2010<br />

If we adjust the flame (oil or gas) so that the output was the capacity theoretically<br />

required, the temperature rise would be<br />

q 144,475<br />

�T � � � 66.5�F<br />

1.08Q 1.08 � 2010<br />

In actual practice, we do not tamper with the flame adjustment in order to<br />

maintain the manufacturer’s design balance. Instead, the amount of air supplied to<br />

each room is in proportion to its load. (See Table 13.12 which is a continuation<br />

of Table 13.11 in the design of a forced-air heating system.) Duct sizes can then<br />

FIGURE 13.5 One-pipe hot-water heating<br />

system.<br />

be determined for the flow indicated in<br />

the table (see Fig. 13.5). In this example,<br />

minimum duct size for practical<br />

purposes is 12 � 3 in. Other duct sizes<br />

were obtained from Table 13.7, for a<br />

friction loss per 100 ft of 0.15, <strong>and</strong><br />

equivalent rectangular sizes were obtained<br />

from Table 13.6 <strong>and</strong> shown in<br />

Fig. 13.5.<br />

Humidification in Warm-Air Heating.<br />

A warm-air heating system lends itself readily to humidification. Most warm-air<br />

furnace manufacturers provide a humidifier that can be placed in the discharge<br />

bonnet of the heater.<br />

Theoretically, a building needs more moisture when the outside temperature<br />

drops. During these colder periods, the heater runs more often, thus vaporizing<br />

more water. During warmer periods less moisture is required <strong>and</strong> less moisture is<br />

added because the heater runs less frequently.<br />

Some manufacturers provide a woven asbestos-cloth frame placed in the pan to<br />

materially increase the contact surface between air <strong>and</strong> water. These humidifiers<br />

have no control.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!