28.02.2013 Views

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

14.60 SECTION FOURTEEN<br />

14.29.2 Sprinkler Piping<br />

There are numerous types of sprinkler piping currently accepted for the installation<br />

of sprinkler systems. In all cases the piping specified for a sprinkler system must<br />

be installed <strong>and</strong> used within the parameters of its U.L. Listing.<br />

Most sprinkler piping specified today is black or galvanized, welded <strong>and</strong> seamless<br />

steel pipe. Normally smaller pipe sizes are specified as Schedule 40 <strong>and</strong> larger<br />

sizes as Schedule 10 black steel pipe. The joining methods for sprinkler pipe include<br />

the use of flanged fittings, prefabricated welded outlets, cast or malleable iron fittings<br />

or mechanical grooved fittings. In all cases, sprinkler pipe <strong>and</strong> fittings must<br />

be capable of withst<strong>and</strong>ing pressures of 175 psi. For further details NFPA 13 <strong>and</strong><br />

pipe manufacturer catalogs should be consulted.<br />

Areas Protected by Sprinklers. To provide a fully sprinklered building, which is<br />

the intent of most building codes <strong>and</strong> insurance industry sprinkler requirements, all<br />

areas of a structure, with few exceptions, must be provided sprinkler protection.<br />

Generally, all spaces that are accessible, combustible or intended for storage or<br />

occupancy require sprinkler protection. The guidelines for permissible sprinkler<br />

omissions in fully sprinkled buildings are contained in NFPA 13. Except for void<br />

spaces in walls <strong>and</strong> noncombustible concealed spaces there are few exceptions <strong>and</strong><br />

where exceptions do exist they are extremely specific with respect to accessibility,<br />

construction <strong>and</strong> dimensions.<br />

With respect to individual sprinkler spacing requirements, the maximum area<br />

protected by one sprinkler should not exceed the area specified for the specific<br />

sprinkler as indicated in the manufacturer’s specification sheets. St<strong>and</strong>ard spray<br />

sprinklers are listed for light hazard, ordinary hazard <strong>and</strong> extra hazard occupancies<br />

for 225-, 130- <strong>and</strong> 100- 2 protection areas, respectively.<br />

In most installations, the area or coverage of each sprinkler is usually less than<br />

the maximum areas listed.<br />

14.29.3 Sprinkler Position<br />

In areas where construction is unobstructed, sprinkler deflectors should be parallel<br />

to <strong>and</strong> within 12 inches of the ceiling. Where construction is obstructed sprinklers<br />

must be within 22 inches of the roof deck above. In all cases, when locating sprinklers<br />

the maximum expected ambient temperature of the area being protected must<br />

be considered such that unwanted sprinkler activation does not occur.<br />

Undesirable sprinkler water spray obstructions must also be considered when<br />

locating sprinklers. Where obstructions such as ducts are greater than 4 feet wide<br />

<strong>and</strong> are located below sprinklers, additional sprinklers should be added to spray<br />

below the obstruction. Furnishings such as tables are not considered obstructions<br />

unless they are within 18-inches, measured vertically of a sprinkler. When locating<br />

all sprinklers NFPA 13 <strong>and</strong> the sprinkler manufacturer’s guidelines must be followed<br />

to prevent unwanted water spray obstructions.<br />

Sprinkler System Layout. A sprinkler system is generally laid out as a ‘‘Tree’’,<br />

‘‘Loop’’ or ‘‘Grid’’ type system. Whatever the case, sprinklers are attached directly<br />

to pipes called branch lines. Branch lines, normally the smallest of sprinkler pipes,<br />

are supplied water from cross mains or feed mains which are directly connected to<br />

the system riser.<br />

The riser, configured to control the water supply <strong>and</strong> monitor water flow <strong>and</strong><br />

valve position, may support a single sprinkler system or if manifolded, many sys-

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!