STRUCTURAL STEEL CONSTRUCTION 7.113<br />

FIGURE 7.54 Effect of rigidity of connections on end moments.<br />

A comparison of fixities intermediate between full rigidity <strong>and</strong> zero restrain in<br />

Fig. 7.54 reveals an optimum condition attainable with 75% rigidity; end <strong>and</strong> centerspan<br />

moments are equal, each being WL/16, or one-half the simple-beam moment.<br />

The saving in weight of beam is quite apparent.<br />

Perhaps the deterrent to a broader usage of semirigid connections has been the<br />

proviso contained in specifications: ‘‘permitted only upon evidence that the connections<br />

to be used are capable of resisting definite moments without overstress of<br />

the fasteners.’’ As a safeguard, the proportioning of the beam joined by such connections<br />

is predicated upon no greater degree of end restraint than the minimum<br />

known to be effected by the connection. Suggested practice, based on research with<br />

welded connections, is to design the end connections for 75% rigidity but to provide<br />

a beam sized for the moment that would result from 50% restraint; i.e., WL/12.<br />

(‘‘Report of Tests of Welded Top Plate <strong>and</strong> Seat <strong>Building</strong> Connections,’’ The Welding<br />

Journal, Research Supplement 146S–165S, 1944.) The type of welded connection<br />

in Fig. 7.52c when designed for the intended rigidity, is generally acceptable.<br />

End-plate connections (Fig. 7.50) are another means of achieving negligible,<br />

partial, <strong>and</strong> full restraint.<br />

7.36 BEAM SPLICES<br />

These are required in rigid frames, suspended-span construction, <strong>and</strong> continuous<br />

beams. Such splices are usually located at points of counterflexure or at points<br />

where moments are relatively small. Therefore, splices are of moderate size. Flanges<br />

<strong>and</strong> web may be spliced with plates or butt welded.