WATER-SUPPLY, SPRINKLER, AND WASTEWATER SYSTEMS 14.61<br />

tems (Fig. 14.19). In any case, the maximum area per floor to be protected by a<br />

single riser is 52,000- 2 for light <strong>and</strong> ordinary hazard areas <strong>and</strong> 40,000- 2 for extra<br />

hazard areas.<br />

In high-rise buildings where st<strong>and</strong>pipes <strong>and</strong> sprinklers are required a combined<br />

st<strong>and</strong>pipe/sprinkler system is normally used. In these situations there may be no<br />

true system riser; rather, each floor is provided with a floor control valve (Fig.<br />

14.20) consisting of a control valve, drain, test connection <strong>and</strong> flow switch. In this<br />

configuration the individual floor control valves accomplish the function of the<br />

system riser. An inherent advantage of using floor control valves is that individual<br />

floors can be isolated so sprinkler system repairs on one floor do not reduce the<br />

level of protection on another floor.<br />

As a practical matter, when lying sprinkler piping out it is advantageous to<br />

consider the pipe hanging arrangement. Where construction consists of joist construction,<br />

mains should be run parallel to the joist channels. This accommodates<br />

FIGURE 14.19 Single riser (left), manifold system with multiple risers (right).<br />

FIGURE 14.20 Floor control valve. (Reprinted with permission from<br />

NFPA 13, Installation of Sprinkler Systems, Copyright � 1996, National<br />

Fire Protection Association, Quincy, MA 02269. This reprinted material<br />

is not the complete <strong>and</strong> official position of the National Fire Protection<br />

Association, on the referenced subject, which is represented only by the<br />

st<strong>and</strong>ard in its entirety.)