28.02.2013 Views

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

WATER-SUPPLY, SPRINKLER, AND WASTEWATER SYSTEMS 14.19<br />

leg to overflow <strong>and</strong> create a discharge siphon; <strong>and</strong> the blowout (Fig. 14.3e), used<br />

with a flushometer valve, which projects a strong jet into the up leg to produce the<br />

discharge. Blowout-type water closets are generally reserved for use where clogs<br />

due to solids in the bowl are common, such as in penal institutions, stadiums, or<br />

arenas. Because of the large amount of water consumed during the flush of a blowout<br />

type of water closet, these types of fixtures are not used to the extent they once<br />

were. Siphon-jet type water closets are the most common type of water closets<br />

specified.<br />

As part of the Energy Policy Act of 1992, all water closets manufactured after<br />

January 1, 1994, for use in the United States were required to have a maximum<br />

water use of 1.6 gallons per flush. Blowout water closets were required to have a<br />

maximum water use of 3.5 gallons per flush <strong>and</strong> urinals were required to have a<br />

maximum water use of 1.0 gallon per flush.<br />

Air Gaps. These should be provided to prevent backflow of wastewater into the<br />

water supply (Art 14.6.4). At plumbing fixtures, an air gap must be provided between<br />

the fixture water-supply outlet <strong>and</strong> the flood-level rim of the receptacle.<br />

<strong>Building</strong> codes usually require a minimum gap of 1 to 2 in for outlets not affected<br />

by a nearby wall <strong>and</strong> from 1 1 ⁄2 to 3 in for outlets close to a wall. Table 14.3 lists<br />

minimum air gaps usually used.<br />

In addition to the usual drain at the lowest point, receptacles generally are provided<br />

with a drain at the flood-level rim to prevent water from overflowing. The<br />

overflow should discharge into the wastewater system on the fixture side of the<br />

trap.<br />

Floor <strong>and</strong> Equipment Drains. Floor drains should be installed at all areas where<br />

the possibility of water spillage occurs. Common areas that are provided with floor<br />

drains include restrooms, mechanical rooms, kitchens, <strong>and</strong> shower <strong>and</strong> locker<br />

rooms. Equipment that requires piped discharge from drains or relief devices, such<br />

as boilers, require recessed-type drains of adequate size, preferably with a funnel<br />

receptor. Large commercial kitchens often require deep, receptor floor sinks to<br />

receive indirect wastes from kitchen equipment.<br />

14.8 WATER DEMAND AND FIXTURE UNITS<br />

For each fixture in a building, a maximum requirement for water flow, gal/min,<br />

can be estimated. Table 14.1 indicates the minimum flow rate <strong>and</strong> pressure required<br />

by code. The maximum flow may be considerably larger. Branch pipes to each<br />

fixture should be sized to accommodate the maximum flow <strong>and</strong> minimum pressure<br />

the fixture will require. Mains serving these branches, however, need not be sized<br />

to h<strong>and</strong>le the sum of the maximum flows for all branches served. It is generally<br />

unlikely that all fixtures would be supplying maximum flow simultaneously or even<br />

that all the fixtures would be operating at the same time. Consequently, the diameters<br />

of the mains need be sized only for the probable maximum water dem<strong>and</strong>.<br />

In practice, the probable flow is estimated by weighting the maximum flow in<br />

accordance with the probability of fixtures being in use. The estimate is based on<br />

the concept of fixture units.<br />

Fixture unit is the average discharge, during use, of an arbitrarily selected fixture,<br />

such as a lavatory or water closet. Once this value is established, the discharge<br />

rates of other types of fixtures are stated in terms of the basic fixture. For example,

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!