28.02.2013 Views

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

15.42 SECTION FIFTEEN<br />

ers for recording current consumed are furnished by the utility company. Unless<br />

otherwise permitted by the utility company, meters must be located near the point<br />

of service entrance. Sometimes, the utility company permits one or more tenant<br />

meter rooms at other locations in the cellar of an apartment house to suit economical<br />

building wiring design. Tenant meter closets on the upper floors, opening on public<br />

halls, also may be permitted. The most common form of tenant meters used is the<br />

three-wire type, consisting of two phase wires <strong>and</strong> the neutral, taken from a 208/<br />

120-V three-phase four-wire service.<br />

The service switch <strong>and</strong> metering equipment may be combined in one unit, or<br />

the switch may be connected with conduit to a separate meter trough. For individual<br />

metering, the detachable-socket-type meter with prongs that fit into the jaws of the<br />

meter-mounting trough generally is used.<br />

15.9.4 Switchboards <strong>and</strong> Panelboards<br />

For low-capacity loads, wiring may be taken directly to a panelboard. For larger<br />

loads, wiring may be brought first to a switchboard <strong>and</strong> then to panelboards. This<br />

equipment is described in Art. 15.7. Branch circuits extend from panelboards to<br />

the various loads.<br />

15.9.5 Sample Calculations for Apartment-<strong>Building</strong> Riser<br />

A diagram of a light <strong>and</strong> power riser for a nine-story apartment building is shown<br />

in Fig. 15.10. Calculation of required wires <strong>and</strong> conduits may be carried out with<br />

the aid of tables in the NFPA ‘‘National Electrical Code H<strong>and</strong>book.’’<br />

1. Typical Meter Branch to Apartment Panel. Note that the meters are threewire<br />

type, <strong>and</strong> three apartments are connected to the same neutral. Under balanced<br />

conditions, when each of the three identical apartments is under full load, no current<br />

will flow in the neutral. But at maximum unbalance, current in the neutral may be<br />

twice the current in the phase wire for any one apartment. The neutral wire must<br />

be sized for this maximum current, though the usual practice is to compute voltage<br />

drops for the balanced condition.<br />

Assume that the apartment area is 900 ft 2 . The one-way run from meter to<br />

apartment panel (apartment A) is 110 ft.<br />

2<br />

Apartment lighting load � 900 � 3 W/ft � 2700 W<br />

Apartment appliance load � 3000<br />

Total � 5700 W<br />

The electric service is three-phase four-wire 208/120 V. Thus, the voltage between<br />

phase wires is 208, <strong>and</strong> between one phase <strong>and</strong> neutral 120 V. Assume a<br />

90% power factor. From Eq. (15.25):<br />

5700<br />

Current per phase � � 26.4 A<br />

2 � 120 � 0.9<br />

The local electrical code requires the minimum size of apartment feeder to be<br />

No. 8 wire. The allowable current in No. 8 RH wire is 45 A; so this wire would<br />

be adequate for the current, but it still must be checked for voltage drop. The neutral<br />

must be sized for the maximum unbalance, under which condition the current in<br />

the neutral will be 2 � 26.4 � 52.8 A. This will require No. 6 wire.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!