13.66 SECTION THIRTEEN<br />

Lights may be assumed to average 4 W/ft 2 . Assume 50 persons will be in the<br />

store, 2 in the first-floor office, 10 in the second-floor office No. 1, <strong>and</strong> 5 in secondfloor<br />

office No. 2.<br />

Cooling Measured in Tons. Once we obtain the cooling load in Btu per hour, we<br />

convert the load to tons of refrigeration by Eq. (13.15).<br />

Cooling Requirements for First-Floor Store (Table 13.15a).<br />

TABLE 13.15a First-Floor Store Load<br />

86,951<br />

Load in tons � � 7.25 tons<br />

12,000<br />

If supply air is provided at 18�F differential, with fresh air entering the unit<br />

through an outside duct, the dehumidified air flow required for sensible heat is<br />

[from Eq. (13.30)]:<br />

Area, ft 2<br />

U(T o � T i),<br />

�F<br />

Heat load,<br />

Btu/hr<br />

Heat gain through enclosures:<br />

North wall 92 � 0.25 � 15 344<br />

North door 28 � 0.46 � 15 193<br />

South wall 412 � 0.25 � 15 1,540<br />

South glass 154 � 1.04 � 15 2,405<br />

East wall 480 � 0.25 � 15 1,800<br />

West wall 228 � 0.25 � 15 854<br />

Partition 263 � 0.39 � 10 1,025<br />

Partition door 49 � 0.46 � 10 225<br />

Floor 841 � 0.25 � 10 2,100<br />

Ceiling 112 � 0.25 � 10 280<br />

Load due to conduction 10,766<br />

Sun load on south glass, 154 ft2 � 98 15,100<br />

Occupants (sensible heat) from Table 13.9, 50 � 315 15,750<br />

Lights [Eq. (13.29)] 841 ft2 � 4 W/ft2 � 3.42 11,500<br />

53,116<br />

Fan hp (4% of total) 2,125<br />

Total internal sensible heat load<br />

Fresh air (sensible heat) at 10 ft<br />

55,241<br />

3 /min per person [Eq. (13.30),*<br />

500 ft3 /min � 1.08 � 15] 8,100<br />

Total sensible load 63,341<br />

Occupants (latent heat) from Table 13.9, 50 � 325 16,250<br />

Fresh air (latent heat) Eq. (13.31), 500 � 0.67(99 � 77) 7,360<br />

Total latent load 23,610<br />

Total load 86,951<br />

* Current criteria typically requires higher levels of ventilation air.