28.02.2013 Views

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

9.132 SECTION NINE<br />

Reinforcement required for flexure of shear walls as a cantilever should be proportioned<br />

as for deep beams (Art. 9.88). Shear reinforcement is usually furnished<br />

as a combination of horizontal <strong>and</strong> vertical bars distributed evenly in each story<br />

(for increment of load). For low shear (where the factored shear force V u at a section<br />

is less than 0.5�V c, where V c is the nominal shear permitted on the concrete), the<br />

minimum shear reinforcement required <strong>and</strong> its location in a wall are the same as<br />

for bearing walls (Art. 9.68). Maximum spacing of horizontal shear reinforcement,<br />

however, should not exceed L w/5, 3h, or 18 in, where L w is the horizontal length<br />

of wall <strong>and</strong> h the overall wall thickness (Fig. 9.56). Maximum spacing of the<br />

vertical reinforcement should not exceed L w/3, 3h, or18in.<br />

A thickness of at least L w/25 is advisable for walls with high shear.<br />

The factored horizontal shear force V u acting on a section through the shear wall<br />

must not exceed the nominal shear strength V n multiplied by � � 0.85.<br />

V � (�V � �V � �V ) (9.110)<br />

u n c s<br />

where V c � nominal shear strength of the concrete <strong>and</strong> V s � nominal shear strength<br />

provided by reinforcement. The horizontal shear strength at any section should not<br />

be taken larger than<br />

V � 10 �ƒ� hd (9.111)<br />

n c<br />

where ƒ�c � specified concrete compressive strength, psi<br />

d � effective depth of wall, but not to be taken larger than 80% of the wall<br />

length<br />

h � wall thickness<br />

Shear carried by the concrete should not exceed the smaller of the values of V c<br />

computed from Eq. (9.112) or (9.113).<br />

Nd u<br />

4Lw V � 3.3 �ƒ� hd � (9.112)<br />

c c<br />

where N u � factored vertical axial load on wall acting with V u, including tension<br />

due to shrinkage <strong>and</strong> creep (positive for compression, negative for tension).<br />

� �<br />

L w(1.25 �ƒ�c � 0.2N u/Lwh) Vc � 0.6 �ƒ� c � hd (9.113)<br />

M /V � L /2<br />

u u w<br />

where Mu � factored moment at section where Vu acts.<br />

Alternatively, Vc � 2 �ƒ�c hd may be used if Nu causes compression. Shear<br />

strength Vc computed for a section at a height above the base equal to Lw/2 or onehalf<br />

the wall height, whichever is smaller, may be used for all lower sections.<br />

When Vu � 0.5�Vc, the area of horizontal shear reinforcement within a distance<br />

s2 required for shear is given by<br />

(V u/��V s)s2 Ah � � 0.0025hs 2<br />

(9.114)<br />

ƒ d<br />

y<br />

where s 2 � spacing of horizontal reinforcement (max � L w/5 � 3h � 18 in) <strong>and</strong><br />

ƒ y � yield strength of the reinforcement.<br />

Also, when V u � 0.5�V c, the area of vertical shear reinforcement with spacing<br />

s should be at least

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!