HEATING, VENTILATION, AND AIR CONDITIONING 13.93<br />

actuation may be economical, particularly for larger valves <strong>and</strong> dampers. When a<br />

pneumatic output signal is required from the controller, a simple digital-topneumatic<br />

relay converts the electronic signal to a variable pressure signal. Pneumatic<br />

actuators provide the additional advantages of excellent reliability <strong>and</strong> low<br />

maintenance cost.<br />

13.37 INDUSTRIAL AIR CONDITIONING<br />

Certain manufacturing processes call for close control of temperature <strong>and</strong> relative<br />

humidity. A typical control system is shown in Fig. 13.45. The humidistat may be<br />

of the single-pole, double-throw type.<br />

On a rise in room humidity, the refrigeration compressor cuts in for the purpose<br />

of dehumidification. Since the sensible capacity of the cooling coil usually is much<br />

higher than the sensible load, whereas the latent capacity does not differ too much<br />

from the latent load, undercooling results. The room thermostat will then send<br />

enough steam or hot water to the reheat coil to maintain proper room temperature.<br />

A small drop in room relative humidity will cut off the compressor. A further<br />

drop in room relative humidity will energize the water or steam solenoid valve to<br />

add moisture to the air. The thermostat is also arranged to cut off all steam from<br />

the reheat coil when the room temperature reaches the thermostat setting. However,<br />

there may be periods when the humidistat will not call for the operation of the<br />

refrigeration compressor <strong>and</strong> the room temperature will climb above the thermostat<br />

setting. An arrangement is provided for the thermostat to cut in the compressor to<br />

counteract the increase in room temperature.<br />

When calculating the load for an industrial system, designers should allow for<br />

the thermal capacity <strong>and</strong> moisture content of the manufactured product entering<br />

<strong>and</strong> leaving the room. Often, this part of the load is a considerable percentage of<br />

the total.<br />

FIGURE 13.45 Circuit for close control of temperature <strong>and</strong> humidity.