14.38 SECTION FOURTEEN<br />

hub; threaded pipe, 12 ft; copper tubing, 10 ft. Supports also should be provided<br />

at the bases of stacks.<br />

Consideration should be given to the possibility of building settlement <strong>and</strong> its<br />

effects on vertical pipes <strong>and</strong> to thermal expansion <strong>and</strong> contraction of pipes, especially<br />

when the pipes have a high coefficient of expansion or are made of copper.<br />

Clean-outs. A clean-out is an opening that provides access to a pipe, either<br />

directly or through a short branch, to permit cleaning of the pipe. The opening is<br />

kept plugged, until the plug has to be removed for cleaning of the sewer. In horizontal<br />

drainage lines, at least one clean-out is required for each 100 ft of pipe.<br />

Clean-outs should be installed at the base of all stacks, at each change of direction<br />

in excess of 45�, <strong>and</strong> at the point where the building sewer begins. For underground<br />

drainage lines, the clean-out must be extended to the floor or ground level to allow<br />

easier cleaning. Clean-outs should open in a direction opposite to that of the flow<br />

in the pipe, or at right angles to it.<br />

In pipes up to 4 in, the clean-out should be the same size as the pipe itself. For<br />

pipes larger than 4 in, the clean-out should be at least 4 in in diameter but may be<br />

larger, if desired. When underground piping over 10 in in diameter is used, an<br />

access hole is required at each 90� bend <strong>and</strong> at intervals not exceeding 150 ft.<br />

14.14 WASTE-PIPE MATERIALS<br />

Cast iron is the most common pipe material for systems in which extremely corrosive<br />

wastes are not expected. Polyvinyl chloride (PVC) is often used because it<br />

is inexpensive, lightweight, <strong>and</strong> easy to install. Galvanized steel, copper, <strong>and</strong> acrylonitrile<br />

butylene styrene (ABS) also are used.<br />

Plumbing piping should conform to one or more of the accepted material st<strong>and</strong>ards<br />

approved by the plumbing code applicable in the area in which the building<br />

is located.<br />

For cast-iron pipe, the fitting joints are calked (with oakum or hemp <strong>and</strong> filled<br />

with molten lead at least 1 in deep), push-on which use rubber gaskets inserted<br />

into the bell of the pipe, or are no-hub (drawn stainless steel b<strong>and</strong>s with neoprene<br />

gaskets). Copper pipe is commonly soldered or brazed, while steel <strong>and</strong> wroughtiron<br />

pipe have screwed, flanged, or welded connections.<br />

When planning a plumbing system, designers should check with the applicable<br />

code before specifying the type of joint to be used in the piping. Joints acceptable<br />

in some areas may not be allowed in others.<br />

14.15 LAYOUT OF WASTE PIPING<br />

Sanitary sewer systems should be sized <strong>and</strong> laid out to permit use of the smallestdiameter<br />

pipes capable of rapidly carrying away the wastewater from fixtures without<br />

clogging the pipes, without creating annoying noises, <strong>and</strong> without producing<br />

excessive pressure fluctuations at points where fixture drains connect to soil or<br />

waste stacks. Such pressure changes may siphon off the liquid seals in traps <strong>and</strong><br />

force sewer gases back through the fixtures into the building. Positive or negative<br />

air pressure at the trap seal of a fixture should never be permitted to exceed 1 in<br />

of water.