9.76 SECTION NINE<br />

TABLE 9.17 Minimum Slab Thickness, in, for Various Fire-Resistive Ratings<br />

Type of concrete<br />

Fire-resistive rating<br />

1 hour 2 hours 3 hours<br />

Normal weight concrete<br />

Top slab thickness*<br />

Siliceous aggregate 3.5 5.0 6.2<br />

Carbonate aggregate 3.2 4.6 5.7<br />

Structural lightweight concrete<br />

Top slab thickness*<br />

S<strong>and</strong>-lightweight 2.7 3.8 4.6<br />

Lightweight 2.5 3.6 4.4<br />

* From Table 7-7-C-C in Uniform <strong>Building</strong> Code Std. 7-7 or Table 709.2.2.1 in St<strong>and</strong>ard <strong>Building</strong> Code.<br />

TABLE 9.18 Minimum <strong>and</strong> Maximum Reinforcement for One-Way Concrete Slabs<br />

Slab<br />

thickness<br />

h, in<br />

Area A s<br />

in 2 /ft<br />

Minimum reinforcement*<br />

Bar size <strong>and</strong><br />

spacing, in<br />

Weight‡<br />

psf<br />

Area A s<br />

in 2 /ft<br />

Maximum reinforcement†<br />

Bar size <strong>and</strong><br />

spacing, in<br />

Weight‡<br />

psf<br />

4 0.086 No. 3 @ 12 � 0.38 0.552 No. 6 @ 9 1 ⁄2 1.90<br />

4 1 ⁄2 0.097 No. 3 @ 13 1 ⁄2 0.33 0.648 No. 6 @ 8 2.25<br />

5 0.108 No. 3 @ 12 0.38 0.744 No. 6 @ 7 2.58<br />

5 1 ⁄2 0.119 No. 3 @ 11 0.41 0.840 No. 6 @ 6 3.00<br />

6 0.130 No. 4 @ 18 0.45 0.924 No. 7 @ 7 1 ⁄2 3.27<br />

6 1 ⁄2 0.140 No. 4 @ 17 0.49 1.020 No. 7 @ 7 3.50<br />

7 0.151 No. 4 @ 15 1 ⁄2 0.52 1.104 No. 8 @ 8 1 ⁄2 3.77<br />

7 1 ⁄2 0.162 No. 4 @ 14 1 ⁄2 0.55 1.200 No. 8 @ 7 1 ⁄2 4.27<br />

8 0.173 No. 4 @ 13 1 ⁄2 0.59 1.284 No. 9 @ 9 4.53<br />

8 1 ⁄2 0.184 No. 4 @ 13 0.62 1.380 No. 9 @ 8 1 ⁄2 4.80<br />

9 0.194 No. 4 @ 12 0.67 1.476 No. 9 @ 8 5.10<br />

* For Grade 60 reinforcement. Minimum area As � 0.0018bh, where b � slab width <strong>and</strong> h � slab<br />

thickness.<br />

†For � 3000 psi; no compression reinforcement; 0.75 �b � 0.016; <strong>and</strong> 3 ⁄4 in concrete cover (not<br />

ƒ�c exposed to weather). Maximum area As � 0.016bd, where d � effective depth of slab.<br />

‡ Weight is based on the bar size <strong>and</strong> spacing for a 1-ft wide by 1-ft length of slab. No transverse<br />

reinforcement is included in the weight.<br />

� This spacing for a 4-in slab is the maximum spacing for flexure but can be increased to 18 in for<br />

temperature <strong>and</strong> shrinkage reinforcement.<br />

if the slab meets ACI 318 <strong>Building</strong> Code requirements for approximate frame analysis<br />

with uniform loads.<br />

For development (bond) of reinforcement, see Art. 9.49.<br />

Shear. Shear strength is usually not critical in one-way slabs carrying uniform<br />

loads, but the ACI 318 <strong>Building</strong> Code requires that it be investigated (see Art.<br />

9.47).