28.02.2013 Views

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

13.80 SECTION THIRTEEN<br />

After all discharge grilles <strong>and</strong> the air-h<strong>and</strong>ling unit are located, it is advisable<br />

to make a single-line drawing of the duct run. The air quantities each line <strong>and</strong><br />

branch must carry should be noted. Of the few methods of duct-system design in<br />

use, the equal-friction method is most practical. For most comfort cooling work, it<br />

is considered good practice not to exceed 0.15-in friction per 100 ft of ductwork.<br />

It is also well to keep the air below 1500 ft/min starting velocity.<br />

If a fresh-air duct is installed the return-air duct should be sized for a quantity<br />

of air equal to the supply air minus the fresh air.<br />

FIGURE 13.36 Ductwork for cooling a store.<br />

It is advisable, where physically possible,<br />

to size the fresh-air duct for the<br />

full capacity of the air-h<strong>and</strong>ling unit.<br />

For example, a 10-ton system h<strong>and</strong>ling<br />

4000 ft3 /min of supply air—1000 ft3 /<br />

min fresh air <strong>and</strong> 3000 ft3 /min return<br />

air—should have the fresh-air duct sized<br />

for 4000 ft3 /min of air. A damper in the<br />

fresh-air duct will throttle the air to<br />

1000 ft3 /min during the cooling season;<br />

however, during an intermediate season,<br />

when the outside air is mild enough,<br />

cooling may be obtained by operating<br />

only the supply-air fan <strong>and</strong> opening the<br />

damper, thus saving the operation of the<br />

10-ton compressor-motor unit.<br />

As an example of the method for sizing<br />

an air-conditioning duct system, let<br />

us determine the ductwork for the first<br />

floor of the building in Fig. 13.36. Although<br />

a load analysis shows that the air<br />

requirement is 2979 ft3 /min, we must<br />

design the ducts to h<strong>and</strong>le the full capacity<br />

of air of the packaged unit we<br />

supply. H<strong>and</strong>ling less air will unbalance<br />

the unit, causing a drop in suction temperature,<br />

<strong>and</strong> may cause freezing up of<br />

the coil. If a 71 ⁄2-ton packaged unit is<br />

used, for example, the ducts should have<br />

a capacity at least equal to the 3000 ft3 /<br />

min at which this unit is rated.<br />

Table 13.17 shows the steps in sizing the ducts. The 3000 ft3 /min is apportioned<br />

to the various zones in the store in proportion to the load from each, <strong>and</strong> the flow<br />

for each segment of duct is indicated in the second column of the table. Next, the<br />

size of an equivalent round duct to h<strong>and</strong>le each airflow is determined from Table<br />

13.8 with friction equal to 0.15 in per 100 ft. The size of rectangular duct to be<br />

used is obtained from Table 13.6.<br />

The preceding example of ductwork design falls into the category of lowpressure<br />

duct systems. This type of design is used for most air-distribution systems<br />

that are not too extensive, such as one- or two-floor systems, offices, <strong>and</strong> residences.<br />

In general, the starting air velocity is below 2000 ft/min, <strong>and</strong> the fan static pressure<br />

is below 3 in of water.<br />

For large multistory buildings, high-velocity air-distribution duct systems often<br />

are used. These systems operate at duct velocities well above 3000 ft/min <strong>and</strong>

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!