CONCRETE CONSTRUCTION 9.95<br />

FIGURE 9.34 Reinforcing bar details for uniformly loaded continuous beams.<br />

At columns, embed alternate bottom bars (at least 50% of the tension-steel area)<br />

a minimum of 6 in., to avoid calculation of development length at 0.125L n.<br />

by splicing the top bars at midspan <strong>and</strong> the bottom bars at or near the supports.<br />

Splicing the bars with Class A tension lap splices (Art. 9.49.7) is acceptable. (See<br />

Fig. 9.35a.)<br />

For nonperimeter beams, the designer has two choices to satisfy the structural<br />

integrity requirements: (1) provide closed stirrups or (2) make at least one-quarter<br />

of the tension-reinforcement area required for positive moment (�A s/4) at midspan<br />

continuous. Splicing the prescribed number of bottom bars over the supports with<br />

Class A tension lap splices is acceptable. At discontinuous ends, the bottom bars<br />

must be anchored with st<strong>and</strong>ard hooks. (see Fig. 9.35b.)<br />

FIGURE 9.35 Reinforcement required to ensure structural integrity of<br />

beams. At least one-sixth of the negative-moment rebars <strong>and</strong> one-fourth of<br />

the positive-moment rebars should be continuous around the perimeter of<br />

the structure (a), with closed stirrups throughout, except at joints. Class A<br />

tension lap splices may be made at midspan. For nonperimeter beams (b),<br />

one-fourth the positive-moment rebars should be continuous. For clarity,<br />

other rebars are not shown in (a) or(b).