28.02.2013 Views

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

15.44 SECTION FIFTEEN<br />

The voltage drop between phase wires can be obtained from Eq. (15.28), with<br />

the area of No. 8 wire taken as 16,510 circular mils <strong>and</strong> length of wire as 110 ft:<br />

�3 � 10.7 � 26.4 � 110<br />

Vd � � 3.24 V<br />

16,510<br />

3.24 � 100<br />

% voltage drop � � 1.56%<br />

208<br />

2. Feeder to Meter Bank on Sixth Floor.<br />

Total load (24 apartments) � 24 � 5700 W � 136,800 W<br />

Dem<strong>and</strong> load: first 15,000 W at 100% � 15,000<br />

Balance, 121,800 W at 50% � 60,900<br />

Total dem<strong>and</strong> load � 75,900 W<br />

Assume a power factor of 90% <strong>and</strong> apply Eq. (15.26):<br />

75,900<br />

Current per phase � � 234 A<br />

3 � 120 � 0.9<br />

Minimum-size type RH wire for this current is 250 kcmil. This has to be tested<br />

for voltage drop. For a one-way run of 150 ft from service switch to sixth-floor<br />

meter bank <strong>and</strong> an area of 250,000 circular mils, Eq. (15.28) gives:<br />

�3 � 10.7 � 234 � 150<br />

Vd � � 2.60 V<br />

250,000<br />

The correction factor for ac resistance of 250-kcmil wire is 1.06. Application of<br />

this factor yields a corrected voltage drop of 1.06 � 2.60 � 2.76 volts.<br />

2.76 � 100<br />

% voltage drop � � 1.33%<br />

208<br />

Then, the total voltage drop from service switch to apartment panel A is<br />

1.56 � 1.33% � 2.89%<br />

which exceeds the 2.5% maximum voltage drop allowed by the local code. It is<br />

necessary, therefore, to increase the size of the meter bank feeder over the minimum<br />

size required for the current.<br />

To bring the total drop down to 2.5% the meter bank feeder drop must be<br />

reduced to 0.94% or 1.96 volts. The required wire size may be found by proportion:<br />

2.76<br />

Required area � � 250,000 � 352,000 circular mils<br />

1.96<br />

The nearest larger wire size is 400 kcmil.<br />

For computing the size of the neutral for carrying 234 A, the local code allows<br />

a dem<strong>and</strong> factor of 70% on lighting loads over 200 A. Hence, the net current in<br />

the neutral is 200 � 34 � 0.70 � 223.8 A. Minimum-size wire is No. 4/0 RH.<br />

And the size of conduit required for the feeder is computed as follows with the aid<br />

of tables in the NFPA ‘‘National Electrical Code H<strong>and</strong>book’’:

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!