HEATING, VENTILATION, AND AIR CONDITIONING 13.69<br />

TABLE 13.15d Second-Floor Office No. 2<br />

Btu/hr<br />

Heat gain through enclosures:<br />

North wall, 103 � 0.25 � 15 386<br />

North glass, 72 � 1.04 � 15 1,110<br />

East wall, 132 � 0.25 � 15 495<br />

Partition, 114 � 0.39 � 10 445<br />

Door in partition, 18 � 0.46 � 10 83<br />

Roof, 231 � 0.19 � 54 2,370<br />

4,889<br />

Occupants (sensible load), 5 � 255 1,275<br />

Lights, 231 � 4 � 3.42 3,160<br />

9,324<br />

Fan hp 4% 373<br />

Total internal sensible load 9,697<br />

Fresh air (sensible load), 77 � 1.08 � 15 1,250<br />

Total sensible load 10,947<br />

Occupants (latent load), 5 � 255 1,275<br />

Fresh air (latent load), 77 � 0.67(99 � 77) 1,140<br />

Total latent load 2,415<br />

Total load 13,362<br />

Cooling <strong>and</strong> supply-air requirements for the building are summarized in Table<br />

13.16.<br />

13.21 REFRIGERATION CYCLES<br />

Figure 13.29 shows the basic air-conditioning cycle of the direct-expansion type.<br />

The compressor takes refrigerant gas at a relatively low pressure <strong>and</strong> compresses<br />

it to a higher pressure. The hot gas is passed to a condenser where heat is removed<br />

<strong>and</strong> the refrigerant liquefied. The liquid is then piped to the cooling coil of the airh<strong>and</strong>ling<br />

unit <strong>and</strong> allowed to exp<strong>and</strong> to a lower pressure (suction pressure). The<br />

liquid vaporizes or is boiled off by the relatively warm air passing over the coil.<br />

TABLE 13.16 Cooling-Load Analysis for <strong>Building</strong> in Fig. 13.3 (p. 13.43)<br />

Space Tons<br />

Flow with ducted<br />

fresh air, ft 3 /min<br />

Flow without<br />

ducted fresh air,<br />

ft 3 /min<br />

First-floor store 7.25 2842 3052<br />

First-floor office 0.35 137 164<br />

Second-floor office No. 1 3.50 1737 1887<br />

Second-floor office No. 2 1.13 499 563<br />

12.23 5215 5666