<strong>ARMY</strong> TM 9-<strong>6115</strong>-<strong>464</strong>-<strong>34</strong><strong>AIR</strong> <strong>FORCE</strong> <strong>35C2</strong>-3-445-2NAVY NAVFAC P-8-624-<strong>34</strong>NOTES:1.2.3.4.5.6.ALL SOLDERED CONNECTIONS SHALL BEIN ACCORDANCE WITH MIL-STD-454,REQUIREMENT 5.CUT INSULATION SLEEVING, FIND NO. 5,IN<strong>TO</strong> 9 PIECES, .750 INCHES LONG ANDINSTALL OVER WIRES AND PINS. AFTERSOLDERING, <strong>TO</strong> THE CONNEC<strong>TO</strong>R, FINDNO. 1. THEN APPLY HEAT OF 400°F FOR3-5 SEC. FOR PROPER SHRINKAGE.INSTALL STRAPS, FIND NO. 4, AT 3.00 MAXINTERVALS AND AT EACH CABLEBREAK-OUT.WIRE MARKING <strong>TO</strong> BE IN ACCORDANCEWITH MlL-W-5088 EXCEPT THAT LENGTHBETWEEN GROUPS OF NUMBERS SHALLNOT EXCEED 6 INCHES.CRIMPED TERMINALS SHALL MEET THEPERFORMANCE REQUIREMENTS OFMIL-T-7928.REFERENCES:A. CONNECTION DIAGRAM: SEE 72-2631.B. SCHEMATIC DIAGRAM: 72-2629, FOR 50/60 Hz.72-2630, FOR 400HzFigure 3-133. Static Exciter Wiring Harness, Dwg. No. 72-2628, Voltage Regulator Wiring Harness,Dwg. No. 72-2627, and Static Exciter Connection Wiring Diagram, Dwg. No. 2-2631 (Sheet 3 of 4)3-282