<strong>ARMY</strong> TM 9-<strong>6115</strong>-<strong>464</strong>-<strong>34</strong><strong>AIR</strong> <strong>FORCE</strong> <strong>TO</strong> <strong>35C2</strong>-3-445-2NAVY NAVFAC P-8-624-<strong>34</strong>Figure 5-26. Load Terminal Board Stud Assemblyb. Test.(1) Remote Battle Short Function.NOTERefer to the Operator and Unit Maintenance Manual for generator set controls andswitches.(a)(b)(c)(d)(e)(f)Close DC circuit breaker.Place START–RUN-S<strong>TO</strong>P switch in RUN position.Place BATTLE SHORT switch in ON position.NOTEThe electric fuel pumps should immediately start to run making a steady clickingsound.Connect test lead from positive terminal of generator set battery to pin D of connector J1 (8, figure5-26).Connect test lead from negative terminal of generator set battery to pin K of connector J1 (8).NOTEThe AC circuit breaker indicator light should light and the electric fuel pumps shouldcontinue to run.Open AC circuit breaker switch.NOTEThe AC circuit breaker indicator light should stay lit and the electric fuel pumps shouldcontinue to run.5-58