<strong>ARMY</strong> TM 9-<strong>6115</strong>-<strong>464</strong>-<strong>34</strong><strong>AIR</strong> <strong>FORCE</strong> <strong>TO</strong> <strong>35C2</strong>-3-445-2NAVY NAVFAC P-8-624-<strong>34</strong>Table 5-1. FUEL BURNING WINTERIZATION KIT TROUBLESHOOTING CHART (Continued)MALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTION3. SWITCH ON, HEATER WILL NOT IGNITE; BLOWER OPERATESStep 1. Defective igniter.Replace igniter (para. 5-4).Step 2. Metering orifice clogged.Clean orifice (para. 5-4).Step 3. Pressure regulator solenoid closed.4. FAN RUNS WITH SWITCH OFFCheck regulator valve. Replace if defective (para. 5-4).Step 1. Broken quartz rod.Replace rod (para. 5-4).Step 2. Flame switch out of adjustment.Adjust flame switch (para 5-4).5. HEATER STARTS, THEN GOES OUT.Step 1.Faulty micro switch.Replace switch (para. 5-4).Step 2.Overheats, trips limit switch.6. CIRCUIT BREAKER OPENSCheck fuel regulator delivery rate. Adjust as required (para. 5-4).Short circuit.7. FAILURE <strong>TO</strong> SHUT OFFDisconnect basic components, one at a time to isolate short (para. 5-4),then check wiring (para. 5-6).Step 1. Fuel regulator valve stuck open.Replace valve (para. 5-4).Step 2. Flame switch stuck open.Adjust or replace (para 5-4).5-2