Acceptance Cnteria<br />

INSFRUMENTAMON AND CONTROL SYMMS<br />

Most non-power reactors can be designed and operated with'an acceptable small<br />

or insignificant radiological risk to the public or to the environment. The SAR<br />

should address the separation and independence of the RCS and the RPS with<br />

consideration of the radiological risk of reactor operation, becauseithese systems<br />

include most of the same types of subsystems and components and similar<br />

functions. If the safety analysis in the SAR shows that safe reactor operation and<br />

safe shutdown would not be compromised by combinationof the two systems,<br />

they need not be separate, independent, or isolated from each other. In practice,<br />

the reactor protection function for non-power reactors has been reliably<br />

accomplished by adding an automatic trip and rod release subsystem to the RCS or<br />

adding safety channels. Since many licensed non-power reactors have been<br />

designed on that principle, this section of the review guidance is based on its<br />

continuing applicability and acceptability.<br />

The acceptance criteria for the RPS should include the following:<br />

* The design bases for the protection function should be provided.<br />

* Detector channels and control elements should be redundant to ensure that<br />

a single random failure or malfunction in the RCS or RPS could not<br />

prevent the RPS from performing its intended function, or prevent safe<br />

reactor shutdown.-<br />

* The logic, schematic, and circuit diagrams should be included and should<br />

-show independence of detector chanmels and trip circuits.<br />

* The RPS is sufficiently distinct in function from 'the RCS that its unique<br />

safety features can be readily tested, verified, and calibrated.<br />

* Technical specifications, including surveillance tests and intervals, 'should<br />

be based on discussions and analyses in the SAR of required safety<br />

functions: :<br />

* The reactor should have operable protection capability in all operating<br />

modes and conditions, as analyzed in the SAR. -For example, at low<br />

reactor power, a reactor period scram may be needed to ensure that<br />

inadvertent transients could not propagate risks to personnel or the reactor.<br />

* The range of operation of sensor (detector) channels should be sufficient to<br />

cover the expected range of variation of the monitored variable during<br />

normal and transient (pulsing or square wave) reactor operation.<br />

REv 0,2/96 .7-Il SThNDARD REvIEW PLAN<br />