CHAR I I<br />

present), or in the unrestricted area would be detected and would initiate<br />

appropriate annunciation or action. The reviewer should coordinate this review<br />

with the Chapter 7 review and should evaluate the design of the radiation<br />

instrumentation systems used for radiation monitoring and dosimetly to verfy<br />

compliance with the acceptance criteria. The reviewer should also verify that these<br />

radiation monitors and alarm systems will be maintained, operated, calibiated, and<br />

subjected to surveillance in compliance with the appropriate standards and are<br />

addressed in the technical specifications.<br />

The reviewer should confirm that the facility warning and annunciator systems are<br />

designed to alert personnel to a radiological hazard or abnormal condition in<br />

sufficient time to enable them to respond in a planned appropriate manner. The<br />

reviewer should also confirm that the interface between the radiation monitoring<br />

system and the engineered safety features (as discussed in Chapter 6) and the<br />

discussion of the radiation monitoring system in the emergency plan are<br />

appropriate.<br />

Evaluation Findings<br />

This section of the SAR should contain sufficient information to support the<br />

following type of conclusion, which will be included in the staffs safety evaluation<br />

report:<br />

* The staff has reviewed the design of radiation monitoring and sampling<br />

provisions at the facility. The fixed and portable equipment used for<br />

radiation monitoring and sampling inside the facility is selected, located,<br />

calibrated, tested, and maintained in accordance with guidance contained in<br />

recognized national standards and the manufacturers' instructions, and with<br />

applicable regulations. The methods and bases of procedures used to<br />

determine the placement of the equipment, the circumstances under which<br />

the equipment is used, and the selection of the equipment function and<br />

sensitivity are appropriate to the facility, and give reasonable assurance that<br />

appropriate types of radiation in significant intensities will be detected,<br />

monitored, and sampled consistent with 10 CFR <strong>Part</strong> 20 requirements and<br />

the facility ALARA program<br />

11.1.5 Radiation Exposure Control and Dosimetry<br />

Areas of Review<br />

The reviewer should verify that the applicant submitted (1) the design bases for the<br />

equipment and procedures utilized for controlling radiation exposures to personnel<br />

and releases of radioactive materials from the facility and (2) dosimetry and<br />

NURBG-<strong>1537</strong>,PART2 11-14 REV. 0,2/96<br />