CHAPrER 8<br />

* The system should be designed to permit safe reactor shutdown and to<br />

prevent uncontrolled release of radioactive material if offsite power is<br />

interrupted or lost. Reactor shutdown is generally achieved by a reactor<br />

scram.<br />

* Electrical power circuits should be isolated sufficiently to avoid<br />

electromagnetic interference with safety-related instrumentation and<br />

control functions.<br />

* Technical specifications should be provided to ensure operability<br />

commensurate with power requirements for reactor shutdown and to<br />

prevent uncontrolled release of radioactive material.<br />

ReWew Procedures<br />

The reviewer should (1) compare the design bases of the normal electrical systems<br />

with the requirements discussed in other chapters of the SAR, including Chapters<br />

4, 5, 7, 9, 10, 11, and 13; (2) confirm that the design characteristics and<br />

components of the normal electrical system could provide the projected range of<br />

services; (3) analyze possible malfunctions, accidents, and interruptions of<br />

electrical services to determine their effect on safe facility operation and on safe<br />

reactor shutdown, and (4) determine if proposed routing and redundancy, if<br />

applicable, of electrical circuits are sufficient to ensure safe reactor operation and<br />

shutdown and to avoid uncontrolled release of radioactive material.<br />

Evaluation Findings<br />

This section of the SAR should contain sufficient information to support the<br />

following types of conclusions, which will be included in the staffs safety<br />

evaluation report:<br />

The design bases and functional characteristics of the normal electrical<br />

power systems for the facility have been reviewed, and the proposed<br />

electrical systems will provide all required services<br />

The design of the normal electrical power system provides that in the event<br />

of the loss or interruption of electrical power the reactor can be safely shut<br />

down.<br />

* The design and location of the electrical wiring will prevent inadvertent<br />

electromagnetic interference between the electrical power service and<br />

safety-related instrumentation and control circuits.<br />

<strong>NUREG</strong>-<strong>1537</strong>,PART2 8-2 REV 0, 2/96