RPLI2D Query effective direction limit 2<br />
WPLI2D0 Set effective direction Min for limit 2<br />
WPLI2D1 Set effective direction Max for limit 2<br />
RPLI2V Query limit 2<br />
WPLI2Vp<br />
RPLI2H<br />
WPLI2Hp<br />
Set limit 2 p<br />
Query limit 1 hysteresis<br />
Set hysteresis limit 1 p<br />
RPLI2CN Query setting of limit contact 2<br />
WPLI2CN0<br />
WPLI2CN1<br />
Set limit contact 2 as normally closed<br />
Set limit contact 2 as normally open<br />
Digital Controller (Option 353, not with Option 483)<br />
RPCITA<br />
WPCITA0<br />
WPCITA1<br />
Query controller type<br />
Type A: Set pulse length controller<br />
Type B: Set pulse frequency controller<br />
RPCIA<br />
WPCIA2<br />
WPCIA3<br />
WPCIAR3<br />
RPCID<br />
WPCIDp<br />
RPCINZ<br />
WPCINZp<br />
RPCILT<br />
WPCILTp<br />
RPCI<strong>LF</strong><br />
WPCI<strong>LF</strong>p<br />
Query controlled variable<br />
Set measuring temperature as controlled variable<br />
Set conductivity as controlled variable<br />
Set resistivity as controlled variable<br />
Query setpoint<br />
Set setpoint p<br />
Query neutral zone<br />
Set neutral zone p<br />
Query minimum ON time<br />
Set minimum ON time p<br />
Query maximum pulse frequency<br />
Set maximum pulse frequency p<br />
Interface Commands 12–21