Information on Electromagnetic Compatibility<br />

Compliance with Interference Immunity<br />

Requirements<br />

All inputs and outputs of the <strong>Process</strong> <strong>Unit</strong> <strong>73</strong> <strong>LF</strong><br />

are electrically isolated to each other. The isolation<br />

voltages are limited to approx. 50 V by gas-filled<br />

surge arresters (to meet EMC requirements to<br />

NAMUR).<br />

Option 351 (Remote Interface)<br />

For connecting the RS 485 interface, twisted<br />

and/or shielded cable must be used.<br />

To meet the radio interference limits at the RS 485<br />

interface, terminal 15 (shield) must be grounded.<br />

Do not use the protective conductor for grounding!<br />

The <strong>Process</strong> <strong>Unit</strong> <strong>73</strong> <strong>LF</strong> meets the following generic<br />

standards:<br />

<br />

<br />

Electromagnetic Emission<br />

EN 50081-1 Domestic, Commercial and Light<br />

Industry<br />

Immunity to Interference<br />

EN 50082-2 Industry<br />

and can therefore be used on residential, commercial<br />

and light industrial premises and in industry.<br />

Information<br />