Trilinear Output Curve<br />
output current [%]<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
0 20 40 60 80 100<br />
conductivity [mS/cm]<br />
To determine the span corresponding to a current<br />
range of 0 (4) to 20 mA, set an initial and an end<br />
value for the process variable.<br />
In addition, you can define two corner points. They<br />
divide the output curve into three regions of different<br />
slopes.<br />
Example:<br />
beginning:<br />
0 mS<br />
1st corner X: 20 mS/cm<br />
1st corner Y: 40 %<br />
2nd corner X: 80 mS/cm<br />
2nd corner Y: 60 %<br />
end:<br />
100 mS<br />
Bilinear Output Curve<br />
output current [%]<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
0 20 40 60 80 100<br />
conductivity [mS/cm]<br />
To define a bilinear output curve, set the same X<br />
and Y values for the two corner points of a trilinear<br />
curve.<br />
To determine the span corresponding to current<br />
range 0 (4) to 20 mA, set an initial and an end value<br />
for the process variable.<br />
In addition, you can define a corner point. It divides<br />
the output curve into two regions of different<br />
slopes.<br />
Example:<br />
beginning:<br />
0 mS<br />
1st corner X: 20 mS/cm<br />
1st corner Y: 40 %<br />
2nd corner X: 20 mS/cm<br />
2nd corner Y: 40 %<br />
end:<br />
100 mS<br />