<strong>Process</strong> <strong>Unit</strong> <strong>73</strong> <strong>LF</strong><br />
Controller Output<br />
The method for determining the controller output<br />
(manipulated variable) is the same for the digital<br />
and the analog controller. However, the output of<br />
the manipulated variable at the limit contacts or at<br />
output 2 differs as follows:<br />
Digital Controller<br />
The controller output (manipulated variable) is output<br />
via the two limit contacts 1 and 2.<br />
Limit contact 1<br />
operates in the controller output range of<br />
0 to +100 %<br />
Controlled variable < setpoint<br />
Limit contact 2<br />
operates in the controller output range of<br />
0 to –100 %<br />
Controlled variable > setpoint<br />
The contacts can control valves of feeding pumps,<br />
for example. Contact ON time or switching frequency,<br />
resp., vary according to the controller output.<br />
The currently valid controller output can be read<br />
out on the secondary display (see page 2–1).<br />
As delivered, the relay contacts are suitable for<br />
low signal currents (down to approx. 1 mA).<br />
If currents above approx. 100 mA are switched,<br />
the gold plating is destroyed during the switching<br />
process. After that, the contacts will not reliably<br />
switch low currents.<br />
Analog Controller<br />
The manipulated variable is output proportionally<br />
as an analog current via output 2.<br />
<br />
<br />
<br />
Controller type A (3-way mixing valve)<br />
operates in the controller output range<br />
–100 to +100 %<br />
Controller type B (straightway valve)<br />
operates in the controller output range<br />
0 to +100 %<br />
Controlled variable < setpoint<br />
Controller type C (straightway valve)<br />
operates in the controller output range<br />
0 to –100 %<br />
Controlled variable > setpoint<br />
9–34 Capabilities