NAMUR Contacts<br />

The three NAMUR contacts functional check,<br />

warning (maintenance required) and failure are<br />

provided as standard.<br />

<br />

<br />

<br />

Functional check is activated:<br />

during calibration (),<br />

during maintenance (): current source,<br />

meas. point maintenance,<br />

during parameter setting () on the<br />

Operator level (opl) and the Administrator level<br />

(adm),<br />

or during an automatic rinsing cycle.<br />

Warning (maintenance required) is activated<br />

if a value has exceeded (or fallen below, resp.)<br />

a preset ”Warning Limit Hi” or ”Warning Limit<br />

Lo”, or if other warning messages have been<br />

activated.<br />

That means that the measuring installation is<br />

still functioning properly but should be maintained,<br />

or that certain process parameters have<br />

reached a value that requires intervention.<br />

Warning is disabled during ”Functional Check”.<br />

Failure is activated<br />

if a value has exceeded (or fallen below, resp.)<br />

a preset ”Failure Limit Hi” or ”Failure Limit Lo”,<br />

if the range limits of the <strong>Process</strong> <strong>Unit</strong> <strong>73</strong> <strong>LF</strong><br />

have been exceeded, or if other failure messages<br />

have been activated.<br />

That means that the measuring installation is<br />

not properly functioning any more, or that certain<br />

process parameters have reached a critical<br />

value.<br />

Failure is disabled during ”Functional Check”.<br />

You can set the three NAMUR contacts as normally<br />

open contacts (active: closed) or as normally<br />

closed contacts (active: open).<br />

For safe operation, the NAMUR contacts must be<br />

set as normally closed contacts.<br />

Only this ensures that power failure will activate<br />

an alarm message!<br />

You can define a delay time for both the warning<br />

and the failure contact . If an alarm message is<br />

released, the contact will only be activated after<br />

this preset delay time.<br />

As delivered, the relay contacts are suitable for<br />

low signal currents (down to approx. 1 mA).<br />

If currents above approx. 100 mA are switched,<br />

the gold plating is destroyed during the switching<br />

process. After that, the contacts will not reliably<br />

switch low currents.<br />

Capabilities 9–29