Enter end of control, corner X, corner Y and reset<br />
time for the right control range (: Controlled variable<br />
> setpoint).<br />
20 mA<br />
Output<br />
2<br />
0(4) mA<br />
Controller output Y [%]<br />
100<br />
Active<br />
50<br />
0<br />
control range<br />
Type B: Straightway valve (< setpoint)<br />
For the straightway valve Type B, the analog controller<br />
output operates in the manipulated variable<br />
range 0 to +100 %. Here, +100 % corresponds to<br />
a current of 20 mA. The controller only outputs the<br />
manipulated variable for the selected side. On the<br />
other side of the setpoint, the manipulated variable<br />
cannot be output and the output remains at<br />
0 (4) mA.<br />
–50<br />
–100<br />
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14<br />
Controlled variable X W [mS/cm]<br />
ÍÍÍÍÍÍÍÍÍÍÍÍ<br />
ÍÍÍÍÍÍÍÍÍÍÍÍ<br />
The parameters of the controlled variable which<br />
controls the controller are set with and .<br />
Press and to choose between the control<br />
parameters. Enter each of the control parameters<br />
with the scrolling and cursor keys (see Pg. 2–5)<br />
and confirm the entries with .<br />
Enter beginning of control, corner X, corner Y and<br />
reset time for the left control range (: Controlled<br />
variable < setpoint).<br />
For a pure P-controller (reset time = 0 s), only the<br />
parameters for the control range used must be<br />
set. However, for the unused range, realistic<br />
parameters must be entered, as otherwise the error<br />
message “Warn Control Parameter” is output.<br />
For use as a PI-controller (reset time 0 s), it is<br />
mandatory that the parameters for the unused<br />
range are also set. The manipulated variable of<br />
both control ranges is influenced by the integration<br />
time.<br />
Capabilities 9–39