Process Unit 73 LF - Knick
Process Unit 73 LF - Knick
Process Unit 73 LF - Knick
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Clock<br />
WCRTThhmmss<br />
WCRTDddmmyy<br />
Set time hhmmss<br />
Set date ddmmyy<br />
Measurement Point Maintenance<br />
WCOM08MA<br />
Enable measurement point maintenance (output currents and controller frozen,<br />
limit values disabled)<br />
Probe Rinsing (Option 352)<br />
WCUCR<br />
Start rinsing cycle<br />
Following commands only with measurement point maintenance enabled (WCOM08MA, RSP = 08):<br />
WCUCCNR0<br />
WCUCCNR1<br />
WCUCCNC0<br />
WCUCCNC1<br />
Open rinsing contact<br />
Close rinsing contact<br />
Open cleaning contact<br />
Close cleaning contact<br />
For setting probe rinsing: see page 12–24<br />
Resistance Measurement<br />
WCOM08R3<br />
Activate resistance measurement<br />
Current Source Function<br />
WCOM08CS<br />
WCCSI1p<br />
Enable current source function<br />
Set output current 1 to value p<br />
WCCSI2p Set output current 2 to value p (only with option 350)<br />
Temperature Probe Adjustment<br />
WCTFVp<br />
Temperature probe adjustment: set process temperature p<br />
For setting temperature probe adjustment:<br />
see page 12–10<br />
Interface Commands 12–27