This section is available on request - MAN Diesel & Turbo
This section is available on request - MAN Diesel & Turbo
This section is available on request - MAN Diesel & Turbo
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>MAN</strong> <strong>Diesel</strong> 4.07<br />
L21/31 GenSet Data<br />
Fig. 4.07.02a: L<str<strong>on</strong>g>is</str<strong>on</strong>g>t of capacities for L21/31, 1,000 rpm<br />
<strong>MAN</strong> B&W 80 → 26 MC/MC�C, 80 → 50 ME/ME�C, 70<br />
→ 60 ME�GI, 50 → 35 ME�B<br />
<strong>MAN</strong> <strong>Diesel</strong><br />
Page 3 of 3<br />
Cyl. 5 6 7 8 9<br />
Maximum c<strong>on</strong>tinuous rating at 1000 rpm kW ,000 ,320 ,540 ,760 ,980<br />
Engine-driven pumps:<br />
LT cooling water pump ( -2.5 bar) m³/h 6 6 6 6 6<br />
HT cooling water pump ( -2.5 bar) m³/h 6 6 6 6 6<br />
Lubricating oil pump (3-5 bar) m³/h 34 34 46 46 46<br />
External pumps:<br />
Max. delivery pressure of cooling water pumps bar 2.5 2.5 2.5 2.5 2.5<br />
<strong>Diesel</strong> oil pump (5 bar at fuel oil inlet A ) m³/h 0.69 0.92 .08 .23 .38<br />
Fuel oil supply pump (4 bar d<str<strong>on</strong>g>is</str<strong>on</strong>g>charge pressure) m³/h 0.34 0.45 0.53 0.60 0.68<br />
Fuel oil circulating pump (8 bar at fuel oil inlet A ) m³/h 0.70 0.93 .09 .25 .40<br />
Cooling capacities:<br />
Lubricating oil kW 206 62 92 222 252<br />
LT charge air kW 25 333 388 443 499<br />
Total LT system kW 33 495 580 665 75<br />
LT flow at 36°C inlet and 44°C outlet* m³/h 35.5 47.8 52. 56.2 60.5<br />
Jacket cooling kW 63 280 332 383 435<br />
HT charge air kW 2 2 36 4 460 509<br />
Total HT system kW 374 64 743 843 944<br />
HT flow at 44°C inlet and 80°C outlet* m³/h 8.9 20.9 23.9 26.7 29.5<br />
Total from engine kW 705 36 323 508 695<br />
LT flow from engine at 36°C inlet m³/h 35.5 47.2 5 .5 55.6 59.9<br />
LT outlet temperature from engine at 36°C inlet °C 53 57 59 60 6<br />
( -string cooling water system)<br />
Gas data:<br />
Exhaust gas flow kg/h 6,920 0,200 ,900 3,600 5,300<br />
Exhaust gas temperature at turbine outlet °C 335 333 333 333 333<br />
Maximum allowable back pressure bar 0.025 0.025 0.025 0.025 0.025<br />
Air c<strong>on</strong>sumpti<strong>on</strong> kg/h 6,720 9,940 ,600 3,200 4,900<br />
Starting air system:<br />
Air c<strong>on</strong>sumpti<strong>on</strong> per start incl. air for jet ass<str<strong>on</strong>g>is</str<strong>on</strong>g>t Nm³ .0 .2 .4 .6 .8<br />
Heat radiati<strong>on</strong>:<br />
Engine kW 2 47 50 54 56<br />
Alternator kW ( See separate data from alternator maker )<br />
The stated heat balances are based <strong>on</strong> 00% load and tropical<br />
c<strong>on</strong>diti<strong>on</strong>.<br />
The mass flows and exhaust gas temperature are based <strong>on</strong> ISO<br />
ambient c<strong>on</strong>diti<strong>on</strong>.<br />
* The outlet temperature of the HT water <str<strong>on</strong>g>is</str<strong>on</strong>g> fixed to 80°C, and<br />
44°C for the LT water.<br />
At different inlet temperature the flow will change accordingly.<br />
Example: If the inlet temperature <str<strong>on</strong>g>is</str<strong>on</strong>g> 25°C then the LT flow will<br />
change to (44-36)/(44-25)* 00 = 42% of the original flow.<br />
The HT flow will not change.<br />
17856 53-3.0<br />
198 42 06�6.4