LBi-5.2: Thermal Comfort & Controls: Occupant Control<br />

Intent To promote projects that provide individual comfort controls for the wellbeing,<br />

productivity and thermal comfort of occupants.<br />

Credit<br />

Requirements GENERAL<br />

For all space types, credits here will only be awarded where LBi-5.1 is achieved.<br />

Demonstrate individual control as follows:<br />

Mechanical Ventilation<br />

The ventilation/temperature control system allows for occupant control over at least air<br />

temperature and / or air speed as follows:<br />

� 1 Credit Point: a minimum of one control per two occupants in the occupied area (only<br />

applies to spaces such as teachers work areas and administrative offices within<br />

schools).<br />

� 1 Credit Point: In addition to the achieving the requirements above, provide occupancy<br />

sensors linked to HVAC control systems that automatically modulate temperature and<br />

air flowrate based on occupancy down to a minimum design setback in all multioccupant<br />

spaces.<br />

Comfort control can be provided by thermostatic controllers linked to on-floor plant or via<br />

supply air terminals directly controllable and easily accessible by occupants that allow<br />

control of temperature and/or flowrate (such as terminals located at floor level, within<br />

workstations or via overhead terminals). Where thermostatic controllers are used in<br />

conjunction with on-floor plant, the plant must be capable of serving no more than two<br />

occupants.<br />

For private enclosed spaces intended for individual use, one thermostatic controller must<br />

be provided that allows control over air speed or temperature as a minimum.<br />

Any fully enclosed individual space that is less than 35m 2 need only have one ventilation /<br />

temperature control system.<br />

In all space types, multi-occupant spaces intended for group activities (meeting rooms,<br />

school classrooms, lecture theatres, conference halls etc) must have at least one<br />

thermostatic controller. Where these spaces have movable internal partitions intended to<br />

sub-divide spaces, each space must have at least one thermostatic controller.<br />

Mixed-mode Ventilation<br />

Where buildings are designed and built for mixed-mode operation to achieve higher energy<br />

savings comply with :<br />

The requirements above for mechanically ventilated buildings, and<br />

� 1 Credit Point: The provision for operable windows as per ASHRAE 62.1.2007,<br />

paragraph 5.1 Natural Ventilation for the 50% of the occupied area.<br />

� 2 Credit Points: The provision for operable windows as per ASHRAE 62.1.2007,<br />

paragraph 5.1 Natural Ventilation for the 75% of the occupied area.<br />

ADDITIONAL REQUIREMENT/CLARIFICATIONS<br />

Retail<br />

All Retail areas are excluded from achieving this credit. For mixed use developments<br />

involving retail spaces submitted under a single application for a <strong>Pearl</strong> <strong>Rating</strong>, project<br />

teams should not include calculations and area schedules associated with retail areas.<br />

Residential<br />

For mechanical ventilation systems meet the requirements of LBi-5.1 Thermal Zones, and<br />

meet the provisions for operable windows as per ASHRAE 62.1.2007 paragraph 5.1 for at<br />