LBi-5.2: Thermal Comfort & Controls: Occupant Control<br />
Intent To promote projects that provide individual comfort controls for the wellbeing,<br />
productivity and thermal comfort of occupants.<br />
Credit<br />
Requirements GENERAL<br />
For all space types, credits here will only be awarded where LBi-5.1 is achieved.<br />
Demonstrate individual control as follows:<br />
Mechanical Ventilation<br />
The ventilation/temperature control system allows for occupant control over at least air<br />
temperature and / or air speed as follows:<br />
� 1 Credit Point: a minimum of one control per two occupants in the occupied area (only<br />
applies to spaces such as teachers work areas and administrative offices within<br />
schools).<br />
� 1 Credit Point: In addition to the achieving the requirements above, provide occupancy<br />
sensors linked to HVAC control systems that automatically modulate temperature and<br />
air flowrate based on occupancy down to a minimum design setback in all multioccupant<br />
spaces.<br />
Comfort control can be provided by thermostatic controllers linked to on-floor plant or via<br />
supply air terminals directly controllable and easily accessible by occupants that allow<br />
control of temperature and/or flowrate (such as terminals located at floor level, within<br />
workstations or via overhead terminals). Where thermostatic controllers are used in<br />
conjunction with on-floor plant, the plant must be capable of serving no more than two<br />
occupants.<br />
For private enclosed spaces intended for individual use, one thermostatic controller must<br />
be provided that allows control over air speed or temperature as a minimum.<br />
Any fully enclosed individual space that is less than 35m 2 need only have one ventilation /<br />
temperature control system.<br />
In all space types, multi-occupant spaces intended for group activities (meeting rooms,<br />
school classrooms, lecture theatres, conference halls etc) must have at least one<br />
thermostatic controller. Where these spaces have movable internal partitions intended to<br />
sub-divide spaces, each space must have at least one thermostatic controller.<br />
Mixed-mode Ventilation<br />
Where buildings are designed and built for mixed-mode operation to achieve higher energy<br />
savings comply with :<br />
The requirements above for mechanically ventilated buildings, and<br />
� 1 Credit Point: The provision for operable windows as per ASHRAE 62.1.2007,<br />
paragraph 5.1 Natural Ventilation for the 50% of the occupied area.<br />
� 2 Credit Points: The provision for operable windows as per ASHRAE 62.1.2007,<br />
paragraph 5.1 Natural Ventilation for the 75% of the occupied area.<br />
ADDITIONAL REQUIREMENT/CLARIFICATIONS<br />
Retail<br />
All Retail areas are excluded from achieving this credit. For mixed use developments<br />
involving retail spaces submitted under a single application for a <strong>Pearl</strong> <strong>Rating</strong>, project<br />
teams should not include calculations and area schedules associated with retail areas.<br />
Residential<br />
For mechanical ventilation systems meet the requirements of LBi-5.1 Thermal Zones, and<br />
meet the provisions for operable windows as per ASHRAE 62.1.2007 paragraph 5.1 for at<br />