Awarding<br />
Credit Points<br />
Credit<br />
Submission:<br />
Design <strong>Rating</strong><br />
Credit<br />
Submission:<br />
Construction<br />
<strong>Rating</strong><br />
least:<br />
� 1 Credit Point: 50% of the living areas and bedrooms within the residential unit.<br />
� 2 Credit Points: 75% of the living areas and bedrooms within the residential unit.<br />
Where any of the living areas have movable internal partitions intended to sub-divide<br />
spaces, each space must have at least one thermostatic controller.<br />
.<br />
CREDIT POINTS REQUIREMENTS<br />
2<br />
(maximum)<br />
1<br />
1<br />
2<br />
(maximum)<br />
1<br />
1<br />
Design <strong>Rating</strong><br />
General: 1 control per 2 occupants<br />
General (Mixed Mode) : 50% occupied area<br />
Residential: Mixed Mode for 50% of living / bedroom areas<br />
Multi-Occupant Spaces (Office, Residential, Schools): 1 control<br />
per space (more if movable partitions present)<br />
Retail: Does not apply to retail.<br />
General: 1 control per 2 occupants & modulating HVAC systems<br />
in multi-occupant spaces<br />
General (Mixed Mode): 75% of occupied area<br />
Residential: Mixed Mode for 75% of living / bed room areas<br />
Multi-Occupant Spaces (Office, Residential, Schools): 1 control<br />
per space (more if movable partitions present)<br />
Retail: Does not apply to retail.<br />
Construction <strong>Rating</strong><br />
General: 1 control per 2 occupants<br />
General (Mixed Mode): 50% of occupied area<br />
Residential: Mixed Mode for 50% of living / bedroom areas<br />
Multi-Occupant Spaces (Office, Residential, Schools): 1 control<br />
per space (more if movable partitions present)<br />
Retail: Does not apply to retail.<br />
General : 1 control per 2 occupants & modulating HVAC systems<br />
in multi-occupant spaces<br />
General (Mixed Mode): 75% of occupied area<br />
Residential: Mixed Mode for 75% of living / bedroom areas<br />
Multi-Occupant Spaces (Office, Residential, Schools): 1 control<br />
per space (more if movable partitions present)<br />
Retail: Does not apply to retail.<br />
Mechanical Ventilation<br />
� Brief narrative describing how the project meets the Credit Requirements;<br />
� Mechanical system drawings showing locations of all air supply terminals and radiant<br />
cooling systems or other individual control devices;<br />
� Plans showing locations of all thermostatic controllers intended for occupant control,<br />
also showing locations of any movable internal walls intended to subdivide spaces; and<br />
� BMS point schedule.<br />
Mixed-mode Ventilation<br />
� All documentation as above for mechanical ventilation; and<br />
� Drawings and elevations clearly indicating the size and location of ventilation openings<br />
and ventilation controls along with open area spreadsheet for each aperture type.<br />
Mechanical Ventilation<br />
� Updated brief narrative describing how the project meets the Credit Requirements;<br />
� As-built mechanical system drawings showing locations of all air supply terminals and<br />
radiant cooling systems or other individual control devices;<br />
<strong>Pearl</strong> <strong>Building</strong> <strong>Rating</strong> <strong>System</strong>: Design & Construction, Version 1.0, April 2010 100 of 223