12.01.2013 Views

Pearl Building Rating System - Estidama

Pearl Building Rating System - Estidama

Pearl Building Rating System - Estidama

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Awarding<br />

Credit Points<br />

Credit<br />

Submission:<br />

Design <strong>Rating</strong><br />

Credit<br />

Submission:<br />

Construction<br />

<strong>Rating</strong><br />

least:<br />

� 1 Credit Point: 50% of the living areas and bedrooms within the residential unit.<br />

� 2 Credit Points: 75% of the living areas and bedrooms within the residential unit.<br />

Where any of the living areas have movable internal partitions intended to sub-divide<br />

spaces, each space must have at least one thermostatic controller.<br />

.<br />

CREDIT POINTS REQUIREMENTS<br />

2<br />

(maximum)<br />

1<br />

1<br />

2<br />

(maximum)<br />

1<br />

1<br />

Design <strong>Rating</strong><br />

General: 1 control per 2 occupants<br />

General (Mixed Mode) : 50% occupied area<br />

Residential: Mixed Mode for 50% of living / bedroom areas<br />

Multi-Occupant Spaces (Office, Residential, Schools): 1 control<br />

per space (more if movable partitions present)<br />

Retail: Does not apply to retail.<br />

General: 1 control per 2 occupants & modulating HVAC systems<br />

in multi-occupant spaces<br />

General (Mixed Mode): 75% of occupied area<br />

Residential: Mixed Mode for 75% of living / bed room areas<br />

Multi-Occupant Spaces (Office, Residential, Schools): 1 control<br />

per space (more if movable partitions present)<br />

Retail: Does not apply to retail.<br />

Construction <strong>Rating</strong><br />

General: 1 control per 2 occupants<br />

General (Mixed Mode): 50% of occupied area<br />

Residential: Mixed Mode for 50% of living / bedroom areas<br />

Multi-Occupant Spaces (Office, Residential, Schools): 1 control<br />

per space (more if movable partitions present)<br />

Retail: Does not apply to retail.<br />

General : 1 control per 2 occupants & modulating HVAC systems<br />

in multi-occupant spaces<br />

General (Mixed Mode): 75% of occupied area<br />

Residential: Mixed Mode for 75% of living / bedroom areas<br />

Multi-Occupant Spaces (Office, Residential, Schools): 1 control<br />

per space (more if movable partitions present)<br />

Retail: Does not apply to retail.<br />

Mechanical Ventilation<br />

� Brief narrative describing how the project meets the Credit Requirements;<br />

� Mechanical system drawings showing locations of all air supply terminals and radiant<br />

cooling systems or other individual control devices;<br />

� Plans showing locations of all thermostatic controllers intended for occupant control,<br />

also showing locations of any movable internal walls intended to subdivide spaces; and<br />

� BMS point schedule.<br />

Mixed-mode Ventilation<br />

� All documentation as above for mechanical ventilation; and<br />

� Drawings and elevations clearly indicating the size and location of ventilation openings<br />

and ventilation controls along with open area spreadsheet for each aperture type.<br />

Mechanical Ventilation<br />

� Updated brief narrative describing how the project meets the Credit Requirements;<br />

� As-built mechanical system drawings showing locations of all air supply terminals and<br />

radiant cooling systems or other individual control devices;<br />

<strong>Pearl</strong> <strong>Building</strong> <strong>Rating</strong> <strong>System</strong>: Design & Construction, Version 1.0, April 2010 100 of 223