RE-7: Global Warming Impacts of Refrigerants<br />

& Fire Suppression <strong>System</strong>s<br />

Intent To promote the selection of refrigerants and fire suppression systems that minimise<br />

impacts on the environment.<br />

Credit<br />

Requirements<br />

GENERAL<br />

Refrigerants<br />

� 1 Credit Point: Demonstrate that the weighted average of all refrigerants to be<br />

installed within the project has an equivalent Global Warming Potential (GWP) of 10<br />

or less.<br />

Refrigerant Leak Detection<br />

� 1 Credit Point: Demonstrate that the project has installed a permanent refrigerant<br />

leak detection system.<br />

Refrigerant Pump Down<br />

� 1 Credit Point: Demonstrate that the project has installed an automatic refrigerant<br />

pump down system to a dedicated storage tank with isolation valves.<br />

Fire Suppression <strong>System</strong>s<br />

� 1 Credit Point: Demonstrate that all gaseous fire suppression systems have a GWP of<br />

1 or less.<br />

Note:<br />

� Where the total collective mass of refrigerant charge used in the project (including<br />

any charge associated with district cooling) is less than 5kg, 1 credit point for<br />

Refrigerants shall be awarded automatically.<br />

� Where only individual units containing less than 5kg of refrigerant are used,<br />

Refrigerant Leak Detection and Refrigerant Pump Down systems are not required, and<br />

those credit points shall be awarded automatically.<br />

� For projects served via district cooling (DC) systems, the points shall only be awarded<br />

if the DC system also complies with the requirements for Refrigerants, Refrigerant<br />

Leak Detection and Refrigerant Pump Down.<br />

� Where no gaseous fire suppression systems are used in the project, the credit point<br />

for Fire Suppression <strong>System</strong>s shall be awarded automatically.<br />

ADDITIONAL REQUIREMENT/CLARIFICATIONS<br />

None<br />