RE-7: Global Warming Impacts of Refrigerants<br />
& Fire Suppression <strong>System</strong>s<br />
Intent To promote the selection of refrigerants and fire suppression systems that minimise<br />
impacts on the environment.<br />
Credit<br />
Requirements<br />
GENERAL<br />
Refrigerants<br />
� 1 Credit Point: Demonstrate that the weighted average of all refrigerants to be<br />
installed within the project has an equivalent Global Warming Potential (GWP) of 10<br />
or less.<br />
Refrigerant Leak Detection<br />
� 1 Credit Point: Demonstrate that the project has installed a permanent refrigerant<br />
leak detection system.<br />
Refrigerant Pump Down<br />
� 1 Credit Point: Demonstrate that the project has installed an automatic refrigerant<br />
pump down system to a dedicated storage tank with isolation valves.<br />
Fire Suppression <strong>System</strong>s<br />
� 1 Credit Point: Demonstrate that all gaseous fire suppression systems have a GWP of<br />
1 or less.<br />
Note:<br />
� Where the total collective mass of refrigerant charge used in the project (including<br />
any charge associated with district cooling) is less than 5kg, 1 credit point for<br />
Refrigerants shall be awarded automatically.<br />
� Where only individual units containing less than 5kg of refrigerant are used,<br />
Refrigerant Leak Detection and Refrigerant Pump Down systems are not required, and<br />
those credit points shall be awarded automatically.<br />
� For projects served via district cooling (DC) systems, the points shall only be awarded<br />
if the DC system also complies with the requirements for Refrigerants, Refrigerant<br />
Leak Detection and Refrigerant Pump Down.<br />
� Where no gaseous fire suppression systems are used in the project, the credit point<br />
for Fire Suppression <strong>System</strong>s shall be awarded automatically.<br />
ADDITIONAL REQUIREMENT/CLARIFICATIONS<br />
None<br />