RE-2: Cool <strong>Building</strong> Strategies<br />

Intent To determine the most effective solution to reducing a building’s cooling demand by<br />

incorporating passive design strategies as a priority.<br />

Credit<br />

Requirements<br />

Awarding Credit<br />

Points<br />

Credit<br />

Submission:<br />

Design <strong>Rating</strong><br />

GENERAL<br />

Demonstrate that passive design measures have been incorporated into the building<br />

design to reduce the external heat gain compared with the baseline building.<br />

Reductions in the annual external heat gain must be analysed and presented according<br />

to the procedure outlined within the Calculations and Methodology section.<br />

� 1-5 Credit Points: Points are awarded based on reductions in the annual external heat<br />

gain of the proposed building compared with the baseline as follows:<br />

Points<br />

Achieved<br />

Percentage<br />

Reduction<br />

1 10%<br />

2 20%<br />

3 30%<br />

4 40%<br />

5 50%<br />

An additional point is awarded for the use of high solar reflective roofing materials in<br />

order to help reduce the building external heat gain as well as the impact on the local<br />

microclimate.<br />

� 1 Credit Point: Use of roofing materials with a Solar Reflectance Index (SRI) � 78<br />

ADDITIONAL REQUIREMENT/CLARIFICATIONS<br />

None<br />

.<br />

CREDIT POINTS REQUIREMENTS<br />

6<br />

(maximum)<br />

1-5<br />

Design <strong>Rating</strong><br />

Demonstrate percentage reductions in annual external heat gain<br />

attributed to passive design measures.<br />

1 Demonstrate that roofing materials with a high SRI will be used.<br />

6<br />

(maximum)<br />

1-5<br />

1<br />

Construction <strong>Rating</strong><br />

Demonstrate percentage reductions in annual external heat gain<br />

attributed to passive design measures.<br />

Demonstrate that roofing materials with a high SRI have been<br />

used.<br />

� Narrative describing the passive design measures to be incorporated within the<br />

project;<br />

� Graph and results table illustrating incremental reductions in the proposed<br />

building’s annual external heat gain (kWh/m 2 ) as outlined within the Calculations<br />

and Methodology section;<br />

� Drawings (section, plan and elevation) as necessary to fully describe all passive<br />

design measures integrated into the building design;<br />

<strong>Pearl</strong> <strong>Building</strong> <strong>Rating</strong> <strong>System</strong>: Design & Construction, Version 1.0, April 2010 151 of 223