LBi-1: Ventilation Quality<br />

Intent To promote the provision of building systems that support the wellbeing and comfort of<br />

occupants by providing sufficient outside air ventilation.<br />

Credit<br />

Requirements<br />

Awarding<br />

Credit Points<br />

GENERAL<br />

Demonstrate that all of the occupied areas meet the following, as appropriate for the<br />

type of ventilation:<br />

Mechanical Ventilation<br />

� 1 Credit Point: Install permanent carbon dioxide (CO2) monitoring and alert systems<br />

to ensure the adequate provision of outside air at all times. At a minimum, one CO2<br />

sensor must be installed at each return point. The CO2 level must not be allowed to<br />

exceed 1000ppm.<br />

� 1 Credit Point: After achieving the above credit point, demonstrate an increase in<br />

outdoor air ventilation of 15% above the outdoor air ventilation rates established in<br />

LBi-R1.<br />

Mixed Mode Ventilation<br />

� 1 Credit Point:<br />

o Comply with the Credit Requirement for CO2 monitoring and alert systems for<br />

mechanically ventilated buildings (above) for the period when the building is<br />

in air conditioned mode; and<br />

o Ensure the CO2 monitoring system has sensors located in the breathing zone<br />

and is capable of alerting occupants when additional fresh air is required. At<br />

a minimum CO2 levels must not exceed 1000ppm; and<br />

o Undertake dynamic simulation modeling (DSM) for the natural ventilation<br />

period of operation, to demonstrate the effectiveness of the operable<br />

window open areas in terms of thermal comfort (as defined for Mixed Mode<br />

buildings in LBi-5.3 Thermal Comfort Modelling), internal CO2 levels and<br />

ventilation rates. Guidance from CIBSE AM10:2005 must be followed for all<br />

natural ventilation strategies. Where a project is located in or has a form<br />

that precludes the assumptions of standard tabulated pressure coefficients<br />

across ventilation openings, the DSM model must be augmented with the<br />

results of either wind tunnel or Computational Fluid Dynamics (CFD)<br />

modeling to establish appropriate pressure coefficients at façade openings.<br />

ADDITIONAL REQUIREMENT/CLARIFICATIONS<br />

None<br />

.<br />

.<br />

CREDIT POINTS REQUIREMENTS<br />

3<br />

Design <strong>Rating</strong><br />

(maximum)<br />

1 CO2 sensors at all return points<br />

1 Ventilation exceeds minimum requirements by 15%<br />

1 Mixed Mode Operation (not available to retail use type)<br />

3<br />

Construction <strong>Rating</strong><br />

(maximum)<br />

1 CO2 sensors at all return points<br />

1 Ventilation exceeds minimum requirements by 15%<br />

1 Mixed Mode Operation (not available to retail use type)<br />