LBi-5.3: Thermal Comfort & Controls: Thermal<br />

Comfort Modeling<br />

Intent To promote projects that are designed to deliver optimal thermal comfort.<br />

Credit<br />

Requirements GENERAL<br />

Demonstrate that thermal modeling has been undertaken during the design process and<br />

that the occupied areas, or living areas and bedrooms for residential spaces, perform as<br />

follows:<br />

Mechanical Ventilation<br />

Demonstrate that the Predicted Mean Vote (PMV) and Predicted Percentage Dissatisfied<br />

(PPD) levels, calculated in accordance with ISO 7730 : 2005, are achieved during standard<br />

operating hours of occupancy for 98% of the year.<br />

� 1 Credit Point: Category C : PMV levels between -0.7 and +0.7 (15% PPD)<br />

� 2 Credit Points: Category B : PMV levels between -0.5 and +0.5 (10% PPD)<br />

Mixed Mode Ventilation<br />

Demonstrate compliance with requirements above for the fully mechanically ventilated<br />

period of operation, and comply with the requirements of ASHRAE 55-2004 section 5.3,<br />

achieving 90% acceptability limits for the naturally ventilated period of operation.<br />

Awarding<br />

Credit Points<br />

Credit<br />

Submission:<br />

Design <strong>Rating</strong><br />

ADDITIONAL REQUIREMENT/CLARIFICATIONS<br />

None<br />

.<br />

CREDIT POINTS REQUIREMENTS<br />

2<br />

(maximum)<br />

1<br />

1<br />

2<br />

(maximum)<br />

1<br />

1<br />

Design <strong>Rating</strong><br />

Category C Performance: PMV levels between -0.7 and +0.7 (15%<br />

PPD) & 90% acceptability limits for Mixed Mode (if applicable).<br />

Category B Performance: PMV levels between -0.5 and +0.5 (10%<br />

PPD) & 90% acceptability limits for Mixed Mode (if applicable).<br />

Construction <strong>Rating</strong><br />

Category C Performance: PMV levels between -0.7 and +0.7 (15%<br />

PPD) & 90% acceptability limits for Mixed Mode (if applicable).<br />

Category B Performance: PMV levels between -0.5 and +0.5 (10%<br />

PPD) & 90% acceptability limits for Mixed Mode (if applicable).<br />

Mechanical Ventilation Period of Operation<br />

� Brief narrative describing how the project meets the Credit Requirements;<br />

� Drawings of the mechanical ventilation systems, clearly indicating zone boundaries and<br />

zone references;<br />

� Screen shots of simulation model Thermal Zones; and<br />

� Spreadsheet listings as per LBi-5.1 augmented with PMV and PPD results from<br />

simulations. Note that zones must match the information provided in Credit LBi-5.1<br />

Thermal Zoning.<br />

Mixed-mode Ventilation Period of Operation<br />

� Brief narrative describing how the project meets the Credit Requirements including<br />

discussion on period of year intended for natural ventilation, mean monthly<br />

temperatures during this period, window control strategy and tables of opening area<br />

per window type;<br />

� Elevation drawings highlighting extent of operable window typologies used per façade;<br />

� Section drawings for each operable window typology showing maximum window<br />

opening position for each operable window type; and<br />

<strong>Pearl</strong> <strong>Building</strong> <strong>Rating</strong> <strong>System</strong>: Design & Construction, Version 1.0, April 2010 102 of 223