LBi-5.3: Thermal Comfort & Controls: Thermal<br />
Comfort Modeling<br />
Intent To promote projects that are designed to deliver optimal thermal comfort.<br />
Credit<br />
Requirements GENERAL<br />
Demonstrate that thermal modeling has been undertaken during the design process and<br />
that the occupied areas, or living areas and bedrooms for residential spaces, perform as<br />
follows:<br />
Mechanical Ventilation<br />
Demonstrate that the Predicted Mean Vote (PMV) and Predicted Percentage Dissatisfied<br />
(PPD) levels, calculated in accordance with ISO 7730 : 2005, are achieved during standard<br />
operating hours of occupancy for 98% of the year.<br />
� 1 Credit Point: Category C : PMV levels between -0.7 and +0.7 (15% PPD)<br />
� 2 Credit Points: Category B : PMV levels between -0.5 and +0.5 (10% PPD)<br />
Mixed Mode Ventilation<br />
Demonstrate compliance with requirements above for the fully mechanically ventilated<br />
period of operation, and comply with the requirements of ASHRAE 55-2004 section 5.3,<br />
achieving 90% acceptability limits for the naturally ventilated period of operation.<br />
Awarding<br />
Credit Points<br />
Credit<br />
Submission:<br />
Design <strong>Rating</strong><br />
ADDITIONAL REQUIREMENT/CLARIFICATIONS<br />
None<br />
.<br />
CREDIT POINTS REQUIREMENTS<br />
2<br />
(maximum)<br />
1<br />
1<br />
2<br />
(maximum)<br />
1<br />
1<br />
Design <strong>Rating</strong><br />
Category C Performance: PMV levels between -0.7 and +0.7 (15%<br />
PPD) & 90% acceptability limits for Mixed Mode (if applicable).<br />
Category B Performance: PMV levels between -0.5 and +0.5 (10%<br />
PPD) & 90% acceptability limits for Mixed Mode (if applicable).<br />
Construction <strong>Rating</strong><br />
Category C Performance: PMV levels between -0.7 and +0.7 (15%<br />
PPD) & 90% acceptability limits for Mixed Mode (if applicable).<br />
Category B Performance: PMV levels between -0.5 and +0.5 (10%<br />
PPD) & 90% acceptability limits for Mixed Mode (if applicable).<br />
Mechanical Ventilation Period of Operation<br />
� Brief narrative describing how the project meets the Credit Requirements;<br />
� Drawings of the mechanical ventilation systems, clearly indicating zone boundaries and<br />
zone references;<br />
� Screen shots of simulation model Thermal Zones; and<br />
� Spreadsheet listings as per LBi-5.1 augmented with PMV and PPD results from<br />
simulations. Note that zones must match the information provided in Credit LBi-5.1<br />
Thermal Zoning.<br />
Mixed-mode Ventilation Period of Operation<br />
� Brief narrative describing how the project meets the Credit Requirements including<br />
discussion on period of year intended for natural ventilation, mean monthly<br />
temperatures during this period, window control strategy and tables of opening area<br />
per window type;<br />
� Elevation drawings highlighting extent of operable window typologies used per façade;<br />
� Section drawings for each operable window typology showing maximum window<br />
opening position for each operable window type; and<br />
<strong>Pearl</strong> <strong>Building</strong> <strong>Rating</strong> <strong>System</strong>: Design & Construction, Version 1.0, April 2010 102 of 223