LBi-7: Daylight & Glare<br />
Intent To promote building designs that maximize the use of natural daylight indoors.<br />
Credit<br />
Requirements<br />
GENERAL<br />
Install daylight sensors to light fittings that receive sufficient daylight illuminance.<br />
Install occupancy sensors in all rooms intended for individual occupancy, conferencing or<br />
meeting rooms, open plan offices spaces and hallways or corridors.<br />
Demonstrate that glare control devices have been designed and installed, such as:<br />
� Automated or manually controlled internal or external glare control devices to all<br />
windows<br />
� Automated glare control devices must be connected to the building management<br />
system<br />
All manually controlled internal glare control devices must be no wider than 4 linear<br />
meters and be directly controllable by occupants.<br />
Demonstrate a minimum daylight illuminance of 250 Lux on the working plane (762mm<br />
from finished floor level) for a percentage of the occupied area, as follows:<br />
� 1 Credit Point: 50% of the occupied area<br />
� 2 Credit Point: 75% of the occupied area<br />
ADDITIONAL REQUIREMENT/CLARIFICATIONS<br />
Occupied area spaces that are specifically intended to avoid daylight, such as auditoria,<br />
can be excluded from calculations.<br />
Retail<br />
All Retail areas are excluded from achieving this credit. For mixed use developments<br />
involving retail spaces submitted under a single application for a <strong>Pearl</strong> <strong>Rating</strong>, project<br />
teams must not include calculations and area schedules associated with retail areas.<br />
Residential<br />
Install occupancy sensors in all communal spaces of the building including hallways.<br />
Demonstrate a minimum daylight illuminance of 200 Lux for each living area (excluding<br />
home theatre) and bedroom (excluding maids’ room) as follows:<br />
� 1 Credit Point: 50% of the net floor area per room and for each room<br />
� 2 Credit Points: 75% of the net floor area per room and for each room<br />
Schools<br />
Install occupancy sensors in all rooms intended for individual occupancy, classrooms, open<br />
plan offices spaces and hallways.<br />
Install glare control devices that comply with general requirements.<br />
Demonstrate that a minimum daylight illuminance of 300 Lux on the working plane<br />
(762mm from finished floor level) for a percentage of the occupied areas as follows:<br />
� 1 Credit Point: 75% of the occupied area<br />
� 2 Credit Point: 90% of the occupied area<br />
<strong>Pearl</strong> <strong>Building</strong> <strong>Rating</strong> <strong>System</strong>: Design & Construction, Version 1.0, April 2010 105 of 223