LBi-7: Daylight & Glare<br />

Intent To promote building designs that maximize the use of natural daylight indoors.<br />

Credit<br />

Requirements<br />

GENERAL<br />

Install daylight sensors to light fittings that receive sufficient daylight illuminance.<br />

Install occupancy sensors in all rooms intended for individual occupancy, conferencing or<br />

meeting rooms, open plan offices spaces and hallways or corridors.<br />

Demonstrate that glare control devices have been designed and installed, such as:<br />

� Automated or manually controlled internal or external glare control devices to all<br />

windows<br />

� Automated glare control devices must be connected to the building management<br />

system<br />

All manually controlled internal glare control devices must be no wider than 4 linear<br />

meters and be directly controllable by occupants.<br />

Demonstrate a minimum daylight illuminance of 250 Lux on the working plane (762mm<br />

from finished floor level) for a percentage of the occupied area, as follows:<br />

� 1 Credit Point: 50% of the occupied area<br />

� 2 Credit Point: 75% of the occupied area<br />

ADDITIONAL REQUIREMENT/CLARIFICATIONS<br />

Occupied area spaces that are specifically intended to avoid daylight, such as auditoria,<br />

can be excluded from calculations.<br />

Retail<br />

All Retail areas are excluded from achieving this credit. For mixed use developments<br />

involving retail spaces submitted under a single application for a <strong>Pearl</strong> <strong>Rating</strong>, project<br />

teams must not include calculations and area schedules associated with retail areas.<br />

Residential<br />

Install occupancy sensors in all communal spaces of the building including hallways.<br />

Demonstrate a minimum daylight illuminance of 200 Lux for each living area (excluding<br />

home theatre) and bedroom (excluding maids’ room) as follows:<br />

� 1 Credit Point: 50% of the net floor area per room and for each room<br />

� 2 Credit Points: 75% of the net floor area per room and for each room<br />

Schools<br />

Install occupancy sensors in all rooms intended for individual occupancy, classrooms, open<br />

plan offices spaces and hallways.<br />

Install glare control devices that comply with general requirements.<br />

Demonstrate that a minimum daylight illuminance of 300 Lux on the working plane<br />

(762mm from finished floor level) for a percentage of the occupied areas as follows:<br />

� 1 Credit Point: 75% of the occupied area<br />

� 2 Credit Point: 90% of the occupied area<br />