PW-2.2: Exterior Water Use Reduction: Heat Rejection<br />

Intent To reduce potable water use for heat rejection by promoting the use of recycled water<br />

and/or alternatives to water-based heat rejection.<br />

Credit<br />

Requirements<br />

Awarding Credit<br />

Points<br />

Credit<br />

Submission:<br />

Design <strong>Rating</strong><br />

GENERAL<br />

Water-Based Heat Rejection<br />

Demonstrate that the following percentage of the projects cooling tower/district<br />

cooling water make-up requirements can be served using the Exterior Water Allowance<br />

(as outlined in the Calculations and Methodology section):<br />

� 2 Credit Points: > 25%<br />

� 3 Credit Points: > 50%<br />

� 4 Credit Points: > 75%<br />

� 5 Credit Points: 100%<br />

AND<br />

Where cooling towers are installed onsite and recycled water is not immediately<br />

available, demonstrate that a recycled water mainline loop has been installed which<br />

allows for the future switch from potable to recycled water in onsite cooling towers<br />

when it becomes available. All pipes containing recycled water must be color coded in<br />

order to easily distinguish them from potable water pipes.<br />

OR<br />

No Water Used for Heat Rejection<br />

� 8 Credit Points: Demonstrate that the project uses no water for heat rejection<br />

ADDITIONAL REQUIREMENT/CLARIFICATIONS<br />

None<br />

CREDIT POINTS<br />

8<br />

(maximum)<br />

2-5<br />

REQUIREMENTS<br />

Design <strong>Rating</strong><br />

Demonstrate that a percentage of the projects cooling<br />

tower/district cooling water make-up requirements can be<br />

served using the Exterior Water Allowance.<br />

8 Demonstrate that no water is required for heat rejection.<br />

8<br />

Construction <strong>Rating</strong><br />

(maximum)<br />

Demonstrate that a percentage of the projects cooling<br />

2-5 tower/district cooling water make-up requirements can be<br />

served using the Exterior Water Allowance.<br />

8 Demonstrate that no water is required for heat rejection.<br />

Water-Based Heat Rejection<br />

� <strong>Building</strong> Water Calculator confirming the percentage of the projects cooling<br />

tower/district cooling water make-up requirements that can be served using the<br />

Exterior Water Allowance; and<br />

� A composite utility schematic illustrating routing of recycled water mainline and<br />

<strong>Pearl</strong> <strong>Building</strong> <strong>Rating</strong> <strong>System</strong>: Design & Construction, Version 1.0, April 2010 129 of 223