5.5 SIMODRIVE POSMO A functions<br />
5.5.12 Standalone mode (without bus communications) (from SW 1.2)<br />
Description<br />
!<br />
Setting the<br />
standalone mode<br />
Safety signals, such as e.g. OFF1 are continually required. This<br />
means, that when bus communications are interrupted, the motor is<br />
immediately shut down with fault. This can be prevented using P100<br />
(simulation of the control word).<br />
Caution<br />
In the standalone mode, when a fault develops, the drive is<br />
automatically reset, i.e. the following applies:<br />
The faults which occur are automatically acknowledged<br />
Before SW 1.3 the following applies: The block sequence is<br />
re–started<br />
From SW 1.3 the following applies: The block sequence is<br />
continued from the next<br />
defined block<br />
If the value of P100 is not equal to zero (e.g. 443Fhex), when powering<br />
up without a master or when the communication fails, after<br />
3 seconds the control word is replaced by this value.<br />
The terminal signals remain active with the highest priority.<br />
For SIMODRIVE POSMO A in the standalone mode, a maximum of 10<br />
traversing blocks can be entered into P101:11 in the range from 3 to<br />
27. In the standalone mode, these specified blocks are executed one<br />
after the other.<br />
Rules when executing the blocks:<br />
Execution sequence: from P101:1 to P101:10<br />
If it is recognized that P101:x = 0, then the last block which is<br />
entered is continuously repeated.<br />
If the block lies within a program range, then the program is executed,<br />
as programmed from this block.<br />
The factory default for P101:11 is as follows (refer to Table 5-9):<br />
Table 5-9 P101:11 (block sequence in the standalone mode)<br />
(factory default)<br />
P101:11<br />
5 Description of the Functions<br />
Index<br />
1 2 3 4 5 6 7 8 9 10<br />
Value 0 0 0 0 0 0 0 0 0 0<br />
5-169<br />